background image

Possible causes for low UV alarm conditions:

a)  The UV lamps have perhaps reached a level whereby they can no longer adequately 

provide a sufficient level of disinfection due to age (> 9000 hours). The lamps 

should be replaced with new lamps from the manufacturer of the same size and 

type.

b)  The quartz sleeves and/or the sensor window have become stained or dirty. 

Mineral deposits or sediment in the water that was not detected during the original 

water analysis may be the cause for this (refer to page 9 for cleaning instructions).

c)  Intermittent voltage drop in the line power supply reducing the lamp output. The 

lamp will return to normal when the power is restored to full voltage. 

Note: the 

monitoring system will not operate during power failures.

d)  The quality of the influent water has changed and is no longer within the 

acceptable operational range of the UV system. Perform a water analysis to 

determine the exact constituents and concentration levels.

e) The UV sensor is not installed correctly (see page

 

10

).

                          

2. Lamp life remaining (days):

To obtain this reading, press the push-button SWITCH a single time and follow the 

steps as outlined on page 

11

, regarding the operation of this feature.

                          

3. Total days of operation:

To obtain this reading, press the push-button SWITCH two times in succession and 

follow steps as outline on page 

11

, regarding the operation of this feature.

                          

4. Lamp failure (blank screen):

Please refer to page 

10

 for explanation of this feature.

Note:

 On the Hi-Flo Monitored systems, the audible tone provided for lamp failure is 

a continuous alarm, rather than the intermittent (1 second on, 1 second off) 

condition on the basic Hi-Flo systems.

5. Solenoid Output:

Working in conjunction with the UV intensity 

monitor, the Hi-Flo Monitored controller 

provides a powered (line voltage) IEC 

solenoid output connector. (Note: this is 

not a dry contact) This solenoid output is 

protected with a replaceable 2 amp isolated 

fuse.  Connection from this output to the 

solenoid can be done using the IEC solenoid 

power cable PN 260184-R. When the UV 

intensity monitor senses that the water is 

not adequately being treated and drops to 

49% UV intensity or below, the internal relay 

is opened thereby stopping AC power flowing to the normally closed solenoid valve. 

The valve will remain closed (no power) until the UV level rises above 

49%, at which time the solenoid will open, allowing for water to pass through. 

(To temporarily enable the operation of this solenoid output for up to 12 hours, 

please refer to the instructions outlined on page 12 of this manual).

 

13

SOLENOID TO BE

INSTALLED ON INLET 

OR OUTLET

INLET/OUTLET

OPTIONAL 

DRAIN COCK

INLET/OUTLET

STERILIGHT

 HI-FLO

CUTOMER SUPPLIED

GFCI CIRCUIT

TO MATCH VOLTAGE

HF

Summary of Contents for SHF-140

Page 1: ...FM 140 SHFM 140 2 SHF 180 SHF 180 2 SHFM 180 SHFM 180 2 425 Clair Rd W Guelph Ontario Canada N1L 1R1 t 1 519 763 1032 tf 1 800 265 7246 US and Canada only t 31 73 747 0144 Europe only f 1 519 763 5069...

Page 2: ...fe coated for stability longer life and increased efficiency Even lamps that look the same will not perform the same Get water confidence with genuine lamps proven to disinfect over their entire lifet...

Page 3: ...ou have taken the first step in ensuring the safety of your water supply by using a totally non intrusive physical disinfection method Your Sterilight system uses the most advanced UV technology on th...

Page 4: ...ce on UV Chamber unless UV chamber has been isolated and depressurized Never service UV Lamps Sleeves or associated hardware until depressurization of UV chamber has been confirmed Hot chamber Allow U...

Page 5: ...gile Eye Protection WEEE waste electrical or electronic equipment This symbol indicates that you should not discard wasted electrical or electronic equipment WEEE in the trash For proper disposal cont...

Page 6: ...d separately 260192 R NORTH AMERICAN NEMA 5 15P 3 PRONG GROUNDED 260198 R CONTINENTAL EUROPEAN CEE 7 7 2 PIN WITH GROUND SCHUKO 260193 R NO CONNECTOR 3 WIRE BARE LEADS 214 fused quartz sleeves with fi...

Page 7: ...is system should only be connected to a properly grounded grounding type power supply receptacle that is protected by a Ground Fault Circuit Interrupter GFCI Inspect operation of GFCI as per manufactu...

Page 8: ...accept the plug from this system Use only extension cords that are intended for outdoor use Use only extension cords having an electrical rating not less than the rating of the system A cord rated for...

Page 9: ...e must be connected to a grounded receptacle and the lamp connector ground wire connected to the stainless steel reactor chamber The disinfection system is designed to be mounted horizontally within t...

Page 10: ...returned to service Please refer to the complete disinfection procedure as outlined on page 7 of this document If the water is to be consumed while the system is off line the water must be boiled for...

Page 11: ...provided Figure 1E 5 Install the UV lamps and UV sensor as outlined on pages 8 10 6 When all plumbing connections are made slowly turn on the water supply and check for leaks The most likely cause fo...

Page 12: ...it is strongly recommended that the entire distribution system located after the UV be chemically disinfected to ensure that the pipework is free from any bacteriological contaminants The disinfectio...

Page 13: ...om the connector simply slide the two apart Avoid touching the lamp on the glass portion Handling the lamp at the ceramic ends is acceptable however if you must touch the lamp glass please use gloves...

Page 14: ...e retaining nuts by turning counter clockwise Figure 3a Drain chamber through drain port Grasp the quartz sleeve and fully remove from the reactor chamber Remove both o rings As with the lamp make sur...

Page 15: ...sensor Disconnect the UV sensor from the Hi Flo Monitored BA ICE M HF controller by disconnecting the sensor cable turning the collar counter clockwise Figure 4B To remove the sensor grasp the body of...

Page 16: ...ired lamp from the reactor chamber dispose of in accordance with local or regional laws and regulations 3 install new UV lamp and connect it to lamp connector refer to page 8 4 replace lamp connector...

Page 17: ...quired to Indicates the UV level is nearing the point of unsafe UV intensity UV system should be immediately serviced Indicates the UV level has now reached a level that is unsafe At this level the wa...

Page 18: ...sh button SWITCH two times in succession and follow steps as outline on page 11 regarding the operation of this feature 4 Lamp failure blank screen Please refer to page 10 for explanation of this feat...

Page 19: ...This Y cable comes with 20 meters 65 of cable for the 4 20 mA signal To install first remove the existing sensor cable from the HF Enclosure Figure 5B and affix the new Y cable Figure 5C Next attach...

Page 20: ...quent use of water run water until it returns to ambient temperature install temperature management valve Water Appears Milky Caused by air in the water lines run water until air is purged Unit Leakin...

Page 21: ...quartz sleeves and sensor eye LED flashing A2 and then back to UV level low UV alarm deferral has been activated UV level has dropped below 50 and the audible alarm has been muted by pressing the res...

Page 22: ...68 lbs 31 8 kg 70 lbs 35 5 kg 78 lbs 36 4 kg 80 lbs Electrical Voltage 100 240V 50 60Hz 100 240V 50 60Hz 100 240V 50 60Hz 100 240V 50 60Hz Power Consumption 350 W 350 W 440 W 440 W Lamp Watts 300 W 30...

Page 23: ...t the problem and identify a solution Please have available the model number system type the date of purchase the name of the dealer from whom you purchased your Sterilight product the source dealer a...

Page 24: ...under these warranties will be covered under warranty up to the end of the warranty period applicable to the original part The above warranties do not include the cost of shipping and handling of retu...

Reviews: