SPECIFICATIONS
Input
(750VA) 120V-1
Φ
- 60Hz; 7A (user resettable circuit breaker)
(1000VA) 120V-1
Φ
- 60Hz; 12A (user resettable circuit breaker)
On Line
Operation
(Input) Limits
92 VAC-146 VAC; 50–60Hz. (auto-sensing) BORIS automatically
maintains consistent output voltage without draining batteries
while operating within these limits.
Transfer Time
2 ms. typical, 4 ms. max.
On-Battery
Output
115 VAC (±5%); 50/60 Hz (±0.1 Hz); 450W–750VA; 670W–
1000VA; sine-wave; overcurrent and short circuit protected,
latching shutdown upon overload.
Battery And
Charger
Spill-proof, maintenance-free, sealed lead-acid battery with 3 to
6 year typical life expectancy; typical recharge time is 2 to 5
hours from total discharge state.
Operating
Environment
0°C-40°C (32°F-104°F) 0-95% humidity (non-condensing)
Dimensions &
Weight
(750VA) 6.2”H x 5.4”W x 14.1”D 29 lbs.
(1000VA) 8.5”H x 6.7”W x 17.3”D 41.5 lbs.
Typical Run
Time Versus
Load
Fully charged
battery at 25°C
(77°F)
LOAD
TIME
(750VA)
TIME
(1000VA)
250 VA
26 MIN
44 MIN
300 VA
20 MIN
36 MIN
350 VA
17 MIN
28 MIN
400 VA
14 MIN
24 MIN
450 VA
11 MIN
20 MIN
500 VA
9 MIN
18 MIN
550 VA
8 MIN
15 MIN
600 VA
6 MIN
13 MIN
700 VA
5 MIN
11 MIN
800 VA 9
MIN
900 VA 7
MIN
1000 VA
6
MIN