 JUPITER PRO 1-3KVA   -   UPS    

www.visionups.com 

10 

6. INSTALLATION AND OPERATING

 

 

6.1.  Installation of the UPS

 

6.1.1. Close every connected equipment (for example the master computer) and pull out the power cord from the 
mains outlet. 
6.1.2. Set up the UPS in a suitable position, with good ventilation and with 30cm space around the vent and fan. 
6.1.3.  The  power  cords  of  the  appliances  which  need  a  UPS  (as  for  example  master  computer,  etc.)  have  to  be 
connected to the output sockets of the UPS.  Others have to be connected to the common mains outlets. 
6.1.4. Connect the input plug of the UPS to the mains outlet.  Make sure that «L - N» (line - neutral) are connected 
the right way and that the grounding cable is ok and well joined. 

 
 

6.2.  Switching on / off 

6.2.1. On mains condition: turn on the input switch on the back side of the UPS.  The unit starts the self-test as well 
as the power output through bypass and reaches normal condition within 15 seconds.  The indicators of power output 
and operating status (green) light up.  The bypass indicator is off.  The user can switch on the computer and other 
loads again.  
6.2.2. On battery condition (main power off): turn on the input switch on the rear of the UPS firstly, and then press 
the start button on the front panel for 3 seconds.  The UPS supplies power through the inverter. 

6.2.2.1.  Daily  start:  press  the  «ON»  button  during  3  seconds.    The  UPS  gives  output  normally  within  15 
seconds. 
6.2.2.2. Daily shut down: press the «OFF» button on the front panel for 3 seconds.  The UPS switches to 
bypass mode when the mains in on.  In this moment the bypass LED is illuminated; otherwise the UPS shuts 
down its operating. 
 

Precautions: 

1)

 

When starting the computer, take care of starting first the UPS and only after then the load of the computer.  
And when switching off, turn off first the computer and afterwards the UPS. 

2)

 

Normally it’s not necessary to shut down the UPS for charging the batteries. 

3)

 

The system transfers to battery mode when mains fails.  Save then your files or undertake other emergency 
activities on your personal computer or on other load appliances.  

 
 

6.3.  Switching on / off after a long storage time of the UPS

 

6.3.1. If 7 days are exceeded shut down the system as follows: press the «OFF» button on the front panel.  Then 
switch on the input breaker on the back panel. 
6.3.2.  Use  the  UPS  after  3  months  of  storage:  start  the  UPS  similarly  as  the  initial  starting  and  ensure  that  it  is 
operating for more than 12 hours in order to charge the batteries.  Keeping the battery in full condition prolongs its 
lifetime. 

 
 

6.4.  Installation of a UPS with long backup 

! Warning: In order to ensure the safety of equipment and persons, the unit has to be installed by qualified technicians! 

6.4.1. Connect the battery cable to the batteries and install them well.      (Note: red is positive, black is negative). 
6.4.2. Plug the UPS into mains outlet, then turn on the switch on the rear panel.  Hereafter, use a  multimeter to 
determinate polarity and voltage, in order to make sure that UPS and battery connector are conform (1.15 times the 
DC voltage measurement of the UPS when the batteries are fully charged). 
 
 

 
 

 
 
 
 
 
 
 
 
 
 

 

Summary of Contents for jupiter pro series

Page 1: ...User Manual Jupiter Pro series 1 3KVA Uninterruptible Power Supply ...

Page 2: ...achieve maximum lifetime of your UPS This manual explains the principle of inner operation and the corresponding protective functions It also contains information about the use of the equipment Please follow the given instructions and warning notices in this manual or on the unit itself Only operate the appliance after you have completely read and understood all the safety and operating instructio...

Page 3: ...nel 7 3 7 Automatic switch off in inverter mode when no load is available optional 7 3 8 Automatic distinction of the output frequency 7 3 9 Battery detection 7 3 10 Intelligent communication ports with intelligent PC assisted monitoring function optional 7 4 Technical specifications 8 5 Product components 9 5 1 Front panel 9 5 2 Back panel 9 6 Installation and operating 10 6 1 Installation of the...

Page 4: ...wall and UPS to avoid any overheating in areas free from flammable gas fume corrosive materials excessive dust conductive contaminants sparks strong vibrations to avoid damages in an interior room with controlled temperature the appliance is not suited for outdoor use no high or low temperatures above 40 C or below 0 C and or with high non condensing humidity above 90 for maintaining the battery l...

Page 5: ...ies are promptly supplying current to the inverter Then after passing through the wave filter the power can be sent to user s equipment without interruption 2 4 Power supply by bypass The bypass mode only happens in the following conditions 1 overload 2 UPS failure 3 Switch on keep pressing the ON button for 3 seconds the UPS will be in process of soft starting within 15 seconds 4 Switch off keep ...

Page 6: ...nging frequency 5 times per second when the batteries are nearly exhausted in order to remind the persons that the batteries are used up and that the UPS will soon cut out When the batteries are almost used up the UPS shuts down automatically to protect the batteries 3 4 Protective functions of the Online UPS Overload on main power condition if the load amounts more than 110 on mains condition the...

Page 7: ...ency 50Hz or 60Hz was before the mains collapsed 3 9 Battery detection The product can work with monitoring software to capture the battery at a certain time In the case of any error message such as an open circuit of battery cable or battery failure the unit can catch the error information through the communication ports to advise the user Meanwhile the UPS has a self protection function by shutt...

Page 8: ...t down within 5s Auto shut down with no load optional 5 shut down within 1min Short circuit System shuts down automatically Alarm AC abnormal Once per 4s silent after 40s Battery low Once per 0 2s Overload Once per 1s Battery DC voltage 24V 24V 36V 48V H 48V configuration standard UPS 2 x 12V7Ah 2 x 12V8Ah 3 x 12V8Ah 4 x 12V8Ah Recharge time 90 capacity after 8 hours Charging current long backup 1...

Page 9: ...when the UPS is working 4 UPS working condition indicator the green light is on when there is main power input the red light is on when there is no mains flowing 5 AC indicator orange the light is on when there is input main power 6 ON starting button start the UPS by pressing the button for 3 seconds The UPS produces output power normally within 15 seconds when starting daily 7 OFF shut down butt...

Page 10: ...n on the front panel for 3 seconds The UPS switches to bypass mode when the mains in on In this moment the bypass LED is illuminated otherwise the UPS shuts down its operating Precautions 1 When starting the computer take care of starting first the UPS and only after then the load of the computer And when switching off turn off first the computer and afterwards the UPS 2 Normally it s not necessar...

Page 11: ...utput power Then cut the main power supply off The UPS transfers automatically to battery mode before shutting down Take note of the discharging time in order to refer it later The total of the load current consumption is calculated in the unit Watt If the marking on the UPS just shows the power capacity in the unit VA then multiply the VA rating with the power factor PF 0 6 for calculating the ra...

Page 12: ...cannot work Whether the battery is not charged or the UPS is not switched on When power has failing computer stops to work Start the UPS when mains is normal Charge the battery during more than 10 hours and then start the UPS When the mains is connected the UPS beeps for 60 seconds and transfers then to bypass When no main power is entering the UPS shuts itself down automatically after 60 seconds ...