7. MAINTENANCE

 

 
7.1.  Preventative maintenance

 

Preventative maintenance of the UPS system can guarantee reliability and a long-time service.  Run some tests per month as 
follows: 

7.1.1. Shut down the UPS (in respect of the operation steps for the details). 
7.1.2. Check that the vents are not blocked. 
7.1.3. Check if there is too much dust covering the surface. 
7.1.4. Check if the plug connections of input, output and batteries are firm, and if the cable insulation is intact. 
7.1.5. Make sure that the UPS is not steaming.  
7.1.6. Start the UPS (in respect of the operation steps for the details). 
7.1.7. Let the UPS working during 5 minutes on battery mode and with a small test load  – until the alarm sounds 
because of low battery voltage.  Whilst  this period should appear no other alarm information; if it  does happen: 
contact the local service centre or the supplier.  

 
 

7.2.  Battery maintenance

 

This unit uses a  sealed lead-acid  battery.  The life time can be reduced because of bad environment  conditions, frequent 
discharges and sharp temperature increase.  The performance of the battery can degrade gradually even when it is not used.  
Therefore we advise to discharge them every 3 months if no mains failure situation occurs for a long time. 
 
Follow the steps below for the maintenance: 

The performance decreases rapidly.  Keep in mind the following work operations of battery maintenance. 

7.2.1. Connect the input main power, switch on the UPS and charge the battery during 8 hours.  Supervise the running 
status of loading which is connected to the UPS. 
7.2.2. Keep the load connected and take note of the total output power.  Then cut the main power supply off.  The 
UPS transfers automatically to battery mode before shutting down.  Take note of the discharging time in order to 
refer it later. 

 

The total of the load (current consumption) is calculated in the unit «Watt». 

 

If the marking on the UPS just shows the power capacity in the unit «VA», then multiply the VA rating with 
the power factor (PF = 0.6) for calculating the rating of «Watt». 

7.2.3.  Under  normal  usage  conditions,  the  battery  lifetime  is  approximately  1-2  years.    But  when  the  battery 
temperature and the discharging frequency are high, then the lifetime is approximately 0.5-1 years.  
7.2.4. The performance of the battery degrades respectively to its running time.  When the discharging time goes 
down to be 80% of its initial time, the performance is degrading quickly.  Therefore the battery maintenance should 
be done every month.   
7.2.5. The battery maintenance of UPS units with long backup: 

(Regular maintenance is vital for the protection of precision equipment under main power off condition.)

 

 

Clear the dust on the battery. 

 

Check if the connecting cables between the batteries are loose or not.  When necessary replace the cable 
or even the battery.   

 

Keep the cable connection to the battery tight. 

 
Note: The discharging test above is just a simple test to check charging status and performance of the battery.  Contact the 
local battery supplier for more detailed information about the battery charging status.   
   
 

7.3. Troubleshooting

 

The UPS can offer a reliability for the load.  In the case of abnormal perturbations it is advisable to contact a local service 
centre to prevent and avoid more damage and nonessential costs.  When the UPS is in abnormal status, you can refer to the 
following  trouble  shootings.    But  if  the  problem  cannot  be  solved,  contact  the  local  distributor  or  contact  our  company 
directly.   
 
 
 
 
 
 
 
 
 
 
 
 
 
 

Summary of Contents for jupiter pro series

Page 1: ...User Manual Jupiter Pro series 1 3KVA Uninterruptible Power Supply ...

Page 2: ...achieve maximum lifetime of your UPS This manual explains the principle of inner operation and the corresponding protective functions It also contains information about the use of the equipment Please follow the given instructions and warning notices in this manual or on the unit itself Only operate the appliance after you have completely read and understood all the safety and operating instructio...

Page 3: ...nel 7 3 7 Automatic switch off in inverter mode when no load is available optional 7 3 8 Automatic distinction of the output frequency 7 3 9 Battery detection 7 3 10 Intelligent communication ports with intelligent PC assisted monitoring function optional 7 4 Technical specifications 8 5 Product components 9 5 1 Front panel 9 5 2 Back panel 9 6 Installation and operating 10 6 1 Installation of the...

Page 4: ...wall and UPS to avoid any overheating in areas free from flammable gas fume corrosive materials excessive dust conductive contaminants sparks strong vibrations to avoid damages in an interior room with controlled temperature the appliance is not suited for outdoor use no high or low temperatures above 40 C or below 0 C and or with high non condensing humidity above 90 for maintaining the battery l...

Page 5: ...ies are promptly supplying current to the inverter Then after passing through the wave filter the power can be sent to user s equipment without interruption 2 4 Power supply by bypass The bypass mode only happens in the following conditions 1 overload 2 UPS failure 3 Switch on keep pressing the ON button for 3 seconds the UPS will be in process of soft starting within 15 seconds 4 Switch off keep ...

Page 6: ...nging frequency 5 times per second when the batteries are nearly exhausted in order to remind the persons that the batteries are used up and that the UPS will soon cut out When the batteries are almost used up the UPS shuts down automatically to protect the batteries 3 4 Protective functions of the Online UPS Overload on main power condition if the load amounts more than 110 on mains condition the...

Page 7: ...ency 50Hz or 60Hz was before the mains collapsed 3 9 Battery detection The product can work with monitoring software to capture the battery at a certain time In the case of any error message such as an open circuit of battery cable or battery failure the unit can catch the error information through the communication ports to advise the user Meanwhile the UPS has a self protection function by shutt...

Page 8: ...t down within 5s Auto shut down with no load optional 5 shut down within 1min Short circuit System shuts down automatically Alarm AC abnormal Once per 4s silent after 40s Battery low Once per 0 2s Overload Once per 1s Battery DC voltage 24V 24V 36V 48V H 48V configuration standard UPS 2 x 12V7Ah 2 x 12V8Ah 3 x 12V8Ah 4 x 12V8Ah Recharge time 90 capacity after 8 hours Charging current long backup 1...

Page 9: ...when the UPS is working 4 UPS working condition indicator the green light is on when there is main power input the red light is on when there is no mains flowing 5 AC indicator orange the light is on when there is input main power 6 ON starting button start the UPS by pressing the button for 3 seconds The UPS produces output power normally within 15 seconds when starting daily 7 OFF shut down butt...

Page 10: ...n on the front panel for 3 seconds The UPS switches to bypass mode when the mains in on In this moment the bypass LED is illuminated otherwise the UPS shuts down its operating Precautions 1 When starting the computer take care of starting first the UPS and only after then the load of the computer And when switching off turn off first the computer and afterwards the UPS 2 Normally it s not necessar...

Page 11: ...utput power Then cut the main power supply off The UPS transfers automatically to battery mode before shutting down Take note of the discharging time in order to refer it later The total of the load current consumption is calculated in the unit Watt If the marking on the UPS just shows the power capacity in the unit VA then multiply the VA rating with the power factor PF 0 6 for calculating the ra...

Page 12: ...cannot work Whether the battery is not charged or the UPS is not switched on When power has failing computer stops to work Start the UPS when mains is normal Charge the battery during more than 10 hours and then start the UPS When the mains is connected the UPS beeps for 60 seconds and transfers then to bypass When no main power is entering the UPS shuts itself down automatically after 60 seconds ...

Reviews: