 JUPITER PRO 1-3KVA   -   UPS    

www.visionups.com 

1. SAFETY & SUMMARY 

 

Follow the instructions below to ensure your own security: 
 

 

Charge the battery longer than 12 hours before using. 

 

After battery discharge or battery storage during more than 3 months, a recharge for 12 hours is required. 

 

The product is designed for group computers and cannot be connected to special loads (for example engines, cooling 
units, etc.). 

 

Keep a minimum distance of 50cm between UPS and monitor to avoid interference.   

 

It is normal that the housing temperature increases to 50°C during operation. 

 

Do not use the UPS with too much charge; don’t overload it. 

 

Do not open the cover in case of danger of electric shock; maintenance and battery replacement should be executed 
only by technicians. 

 

Inner short circuit may cause electric shock or fire danger.   

 

Do  not  let  attain  any  liquids  or  foreign  objects  into  the  UPS  appliance;  that’s  why  no  beverage  or  other  liquid-
containing vessels should be placed on or near the appliance.   

 

Disconnect directly the power supply if the unit works abnormal.   

 

Ensure that the unit is only installed and used in environments with the following conditions: 

-

 

a good circulation of air around the UPS, means do not block the UPS, keep all ventilations openings 
free, keep a minimum distance of 30cm between wall and UPS to avoid any overheating; 

-

 

in areas free from: flammable gas, fume, corrosive materials, excessive dust, conductive contaminants, 
sparks, strong vibrations – to avoid damages; 

-

 

in an interior room with controlled temperature (the appliance is not suited for outdoor use); 

-

 

no  high  or  low  temperatures  (above  40°C  or  below  0°C)  and/or  with  high  non-condensing  humidity 
(above 90%)  – for maintaining the battery lifetime, we advise an ambient  operating temperature of 
20°C to 25°C; 

-

 

no direct sunlight and not near to heat emitting appliances such as space heaters or furnaces/ovens.  

 

Use power extinguishers in the case of fire around the UPS.   
(DO NOT USE extinguishers based on liquids because of the risk of electric shock!). 

 

The mains socket outlet that supplies the UPS shall be installed near the UPS unit, in order that you can easily access 
in emergency situation to remove the plug from socket and cut off the power supply. 

 

The product can provide 100% of power output with a voltage rating of +/-25%.  If out of this range, the output power 
is as follows: 

   

 
 
  
 
 
 
 
 
 
 
 

 

 
 
 

WARNING!  The equipment must be connected to the ground: 
 

1.

 

The  equipment  must  be  connected  to  the  ground.    Ensure  that  the  UPS  correctly  earthed  before 
connecting the mains to supply the appliance. 

2.

 

The power socket must be 15A/250V – or above this if the capacity of the UPS is more than 2KVA.  

3.

 

Incorrect operation may cause heavy loss.  Ensure to use the UPS correctly according to this manual.   

 
 
 
 
 
 
 
 
 
 
 
 
   

 

 

100%

75%

50%

25%

P(

)

145

175

280

U(v)

Input voltage and output power 

Summary of Contents for jupiter pro series

Page 1: ...User Manual Jupiter Pro series 1 3KVA Uninterruptible Power Supply ...

Page 2: ...achieve maximum lifetime of your UPS This manual explains the principle of inner operation and the corresponding protective functions It also contains information about the use of the equipment Please follow the given instructions and warning notices in this manual or on the unit itself Only operate the appliance after you have completely read and understood all the safety and operating instructio...

Page 3: ...nel 7 3 7 Automatic switch off in inverter mode when no load is available optional 7 3 8 Automatic distinction of the output frequency 7 3 9 Battery detection 7 3 10 Intelligent communication ports with intelligent PC assisted monitoring function optional 7 4 Technical specifications 8 5 Product components 9 5 1 Front panel 9 5 2 Back panel 9 6 Installation and operating 10 6 1 Installation of the...

Page 4: ...wall and UPS to avoid any overheating in areas free from flammable gas fume corrosive materials excessive dust conductive contaminants sparks strong vibrations to avoid damages in an interior room with controlled temperature the appliance is not suited for outdoor use no high or low temperatures above 40 C or below 0 C and or with high non condensing humidity above 90 for maintaining the battery l...

Page 5: ...ies are promptly supplying current to the inverter Then after passing through the wave filter the power can be sent to user s equipment without interruption 2 4 Power supply by bypass The bypass mode only happens in the following conditions 1 overload 2 UPS failure 3 Switch on keep pressing the ON button for 3 seconds the UPS will be in process of soft starting within 15 seconds 4 Switch off keep ...

Page 6: ...nging frequency 5 times per second when the batteries are nearly exhausted in order to remind the persons that the batteries are used up and that the UPS will soon cut out When the batteries are almost used up the UPS shuts down automatically to protect the batteries 3 4 Protective functions of the Online UPS Overload on main power condition if the load amounts more than 110 on mains condition the...

Page 7: ...ency 50Hz or 60Hz was before the mains collapsed 3 9 Battery detection The product can work with monitoring software to capture the battery at a certain time In the case of any error message such as an open circuit of battery cable or battery failure the unit can catch the error information through the communication ports to advise the user Meanwhile the UPS has a self protection function by shutt...

Page 8: ...t down within 5s Auto shut down with no load optional 5 shut down within 1min Short circuit System shuts down automatically Alarm AC abnormal Once per 4s silent after 40s Battery low Once per 0 2s Overload Once per 1s Battery DC voltage 24V 24V 36V 48V H 48V configuration standard UPS 2 x 12V7Ah 2 x 12V8Ah 3 x 12V8Ah 4 x 12V8Ah Recharge time 90 capacity after 8 hours Charging current long backup 1...

Page 9: ...when the UPS is working 4 UPS working condition indicator the green light is on when there is main power input the red light is on when there is no mains flowing 5 AC indicator orange the light is on when there is input main power 6 ON starting button start the UPS by pressing the button for 3 seconds The UPS produces output power normally within 15 seconds when starting daily 7 OFF shut down butt...

Page 10: ...n on the front panel for 3 seconds The UPS switches to bypass mode when the mains in on In this moment the bypass LED is illuminated otherwise the UPS shuts down its operating Precautions 1 When starting the computer take care of starting first the UPS and only after then the load of the computer And when switching off turn off first the computer and afterwards the UPS 2 Normally it s not necessar...

Page 11: ...utput power Then cut the main power supply off The UPS transfers automatically to battery mode before shutting down Take note of the discharging time in order to refer it later The total of the load current consumption is calculated in the unit Watt If the marking on the UPS just shows the power capacity in the unit VA then multiply the VA rating with the power factor PF 0 6 for calculating the ra...

Page 12: ...cannot work Whether the battery is not charged or the UPS is not switched on When power has failing computer stops to work Start the UPS when mains is normal Charge the battery during more than 10 hours and then start the UPS When the mains is connected the UPS beeps for 60 seconds and transfers then to bypass When no main power is entering the UPS shuts itself down automatically after 60 seconds ...