 JUPITER PRO 1-3KVA   -   UPS    

www.visionups.com 

3.5.  Function to follow the phase

 

On main power condition, the system measures the phase voltage, which guarantees in the case of a current interruption that 
the produced output voltage goes the same voltage curve as before the mains did.  This can reduce the overvoltage, which 
was produced between mains current (AC) and batteries, and ensures like that the best possible protection of the equipment. 
 
 

3.6.  LCD and LED display panel   

The  intuitive  LED  and  LCD  displays  communicate  quick  and  easy  information  about  battery  capacity,  charge  capacity  and 
working status of the whole system to the user.   
 
 

3.7. Automatic switch-off in inverter mode when no load is available - (optional)

 

When the UPS is in inverter mode, the system cuts the alarm after 40s and reads at the same time automatically the load 
capacity.  If the load amounts less than 5%, the UPS unit considers this as no load and ceases its operation automatically after 
1 minute for the purpose of recharging the battery and prolonging the battery lifetime. 
 
 

3.8.  Automatic distinction of the output frequency

 

The  mains  frequency  is  50Hz  or  60Hz.    When  the  UPS  is  connected  with  the  mains,  it  detects  automatically  the  mains 
frequency.   The output frequency of the unit stays the same as the mains frequency (50Hz or 60Hz) was before the mains 
collapsed. 
 
 

3.9.  Battery detection

 

The product can work with monitoring software to capture the battery at a certain time.  In the case of any error message, 
such as an open circuit of battery cable or battery failure, the unit can catch the error information through the communication 
ports to advise the user. 

Meanwhile, the UPS has a self-protection function by shutting down the charging system and switching into the bypass mode 
(concerns the UPS model with bypass function).  At normal main power, the system is supplied by bypass and the LCD display 
shows «PWR DN», as well as the icon «

!

» or the word «full». 

 
 

3.10.  Intelligent communication ports (with intelligent PC-assisted monitoring function) - (optional)

 

This series of UPS can be monitored/controlled by PC through RS232, USB or SNMP card.  It provides an ON/OFF control and 
an auto-file-saving function for different kinds of systems like WINDOWS 98 / NT / 2000 / ME / 2003 / XP / Vista. 

1.

 

In addition to other UPS operating data (LCD UPS), this series of UPS can automatically detect the condition of the 
failed mains and of the battery in low voltage. 

2.

 

When the mains fails, the system completes a countdown of auto-file-saving and shut down of system and UPS. 

3.

 

The UPS can set a supplying time to the system and can record event storages of the UPS working status and of the 
mains status etc. 

When the computer operating system is in shut-down-countdown, it can set a determined remaining time before the cut-off 
of the UPS. 

 

 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 

 

Summary of Contents for jupiter pro series

Page 1: ...User Manual Jupiter Pro series 1 3KVA Uninterruptible Power Supply ...

Page 2: ...achieve maximum lifetime of your UPS This manual explains the principle of inner operation and the corresponding protective functions It also contains information about the use of the equipment Please follow the given instructions and warning notices in this manual or on the unit itself Only operate the appliance after you have completely read and understood all the safety and operating instructio...

Page 3: ...nel 7 3 7 Automatic switch off in inverter mode when no load is available optional 7 3 8 Automatic distinction of the output frequency 7 3 9 Battery detection 7 3 10 Intelligent communication ports with intelligent PC assisted monitoring function optional 7 4 Technical specifications 8 5 Product components 9 5 1 Front panel 9 5 2 Back panel 9 6 Installation and operating 10 6 1 Installation of the...

Page 4: ...wall and UPS to avoid any overheating in areas free from flammable gas fume corrosive materials excessive dust conductive contaminants sparks strong vibrations to avoid damages in an interior room with controlled temperature the appliance is not suited for outdoor use no high or low temperatures above 40 C or below 0 C and or with high non condensing humidity above 90 for maintaining the battery l...

Page 5: ...ies are promptly supplying current to the inverter Then after passing through the wave filter the power can be sent to user s equipment without interruption 2 4 Power supply by bypass The bypass mode only happens in the following conditions 1 overload 2 UPS failure 3 Switch on keep pressing the ON button for 3 seconds the UPS will be in process of soft starting within 15 seconds 4 Switch off keep ...

Page 6: ...nging frequency 5 times per second when the batteries are nearly exhausted in order to remind the persons that the batteries are used up and that the UPS will soon cut out When the batteries are almost used up the UPS shuts down automatically to protect the batteries 3 4 Protective functions of the Online UPS Overload on main power condition if the load amounts more than 110 on mains condition the...

Page 7: ...ency 50Hz or 60Hz was before the mains collapsed 3 9 Battery detection The product can work with monitoring software to capture the battery at a certain time In the case of any error message such as an open circuit of battery cable or battery failure the unit can catch the error information through the communication ports to advise the user Meanwhile the UPS has a self protection function by shutt...

Page 8: ...t down within 5s Auto shut down with no load optional 5 shut down within 1min Short circuit System shuts down automatically Alarm AC abnormal Once per 4s silent after 40s Battery low Once per 0 2s Overload Once per 1s Battery DC voltage 24V 24V 36V 48V H 48V configuration standard UPS 2 x 12V7Ah 2 x 12V8Ah 3 x 12V8Ah 4 x 12V8Ah Recharge time 90 capacity after 8 hours Charging current long backup 1...

Page 9: ...when the UPS is working 4 UPS working condition indicator the green light is on when there is main power input the red light is on when there is no mains flowing 5 AC indicator orange the light is on when there is input main power 6 ON starting button start the UPS by pressing the button for 3 seconds The UPS produces output power normally within 15 seconds when starting daily 7 OFF shut down butt...

Page 10: ...n on the front panel for 3 seconds The UPS switches to bypass mode when the mains in on In this moment the bypass LED is illuminated otherwise the UPS shuts down its operating Precautions 1 When starting the computer take care of starting first the UPS and only after then the load of the computer And when switching off turn off first the computer and afterwards the UPS 2 Normally it s not necessar...

Page 11: ...utput power Then cut the main power supply off The UPS transfers automatically to battery mode before shutting down Take note of the discharging time in order to refer it later The total of the load current consumption is calculated in the unit Watt If the marking on the UPS just shows the power capacity in the unit VA then multiply the VA rating with the power factor PF 0 6 for calculating the ra...

Page 12: ...cannot work Whether the battery is not charged or the UPS is not switched on When power has failing computer stops to work Start the UPS when mains is normal Charge the battery during more than 10 hours and then start the UPS When the mains is connected the UPS beeps for 60 seconds and transfers then to bypass When no main power is entering the UPS shuts itself down automatically after 60 seconds ...