 JUPITER PRO 1-3KVA   -   UPS    

www.visionups.com 

4. TECHNICAL SPECIFICATIONS

 

 

Model 

1000VA/h 

1500VA/h 

2000VA/h 

3000VA/h 

Real power rating 

600W 

900W 

1200W 

1800W 

Display 

Indicator on panel 

LED / LCD plus LED display 

AC-Mode 

Types of load 

Ancillary equipment such as PC, display, group computers, etc. 

Input voltage 

100V/110V/120V/220V/230V/240V ±25%: (-35%+25% optional) 

Input frequency 

45-65Hz (transfer to battery mode if out of this range) 

Output voltage 

100V/110V/120V/220V/230V/240V ±25% 

Input PF(AC/DC) 

98% 

Efficiency 

≥96% (AC-Mode) 

Overload in AC-Mode 

110% transfer to bypass within 60s                                                                               
120% transfer to bypass within 30s                                                 
Automatic recovering if the load capacity becomes normal 

Short circuit 

Protected by input fuse 

Inverter-Mode 

Output voltage 

100V/110V/120V/220V/230V/240V ±5% 

Output frequency 

50Hz/60Hz ±1% self-adaptive 

Output PF 

=0.6 

Waveform distortion 

≤5% linear load 

Battery backup time 

≥10min (PC load) 

Transfer time 

Typical value: 5ms, max : 8ms 

Efficiency 

≥80% (INV mode) 

Overload in INV mode 

110% shut down within 60s                                                        
120% shut down within 5s 

Auto shut down with no load (optional) 

<5% shut down within 1min 

Short circuit 

System shuts down automatically 

Alarm 

AC abnormal 

Once per 4s, silent after 40s 

Battery low 

Once per 0.2s 

Overload 

Once per 1s  

Battery 

DC voltage 

24V 

24V 

36V         48V(H)  48V 

configuration    (standard UPS) 

2 x 12V7Ah 

2 x 12V8Ah 

3 x 12V8Ah 

4 x 12V8Ah 

Recharge time 

90% capacity after 8 hours 

Charging current (long backup) 

10A, maximum 

Communication (charging option) 

RS232 / USB / SNMP (can be programmed with automatic UPS turn 
on/off) 

Miscellaneous 

Output sockets 

Customized, on request 

Surge protection  

Optional 

EMC 

EN62040-2:2006; EN61000-3-2:2006; EN61000-3-3:2008 

IP level 

IP20 

Ambient temperature 

0°C ~ 40°C 

Ambient humidity 

10% ~ 90% (no condensing) 

Noise level 

≤45dB 

Dimensions (mm) D*W*H 

355x145x215 

Dimensions (mm) 
D*W*H 

355x145x215 

Packing dimensions D*W*H (mm) 

427x325x245 

Packing dimensions 
D*W*H (mm) 

427x325x245 

Net weight (kg) 

14.5 

Net weight (kg)  14.5 

Net weight (kg) 

Gross weight (kg) 

15.5 

Gross weight 
(kg) 

15.5 

Gross weight 
(kg) 

Notes: 

1)

 

Data with «(H)» indicate, that the UPS is a long backup type with external battery. 

2)

 

Above named data  are concerning UPS  standard units, which  can vary in accordance with the special units from 
customers.  

Summary of Contents for jupiter pro series

Page 1: ...User Manual Jupiter Pro series 1 3KVA Uninterruptible Power Supply ...

Page 2: ...achieve maximum lifetime of your UPS This manual explains the principle of inner operation and the corresponding protective functions It also contains information about the use of the equipment Please follow the given instructions and warning notices in this manual or on the unit itself Only operate the appliance after you have completely read and understood all the safety and operating instructio...

Page 3: ...nel 7 3 7 Automatic switch off in inverter mode when no load is available optional 7 3 8 Automatic distinction of the output frequency 7 3 9 Battery detection 7 3 10 Intelligent communication ports with intelligent PC assisted monitoring function optional 7 4 Technical specifications 8 5 Product components 9 5 1 Front panel 9 5 2 Back panel 9 6 Installation and operating 10 6 1 Installation of the...

Page 4: ...wall and UPS to avoid any overheating in areas free from flammable gas fume corrosive materials excessive dust conductive contaminants sparks strong vibrations to avoid damages in an interior room with controlled temperature the appliance is not suited for outdoor use no high or low temperatures above 40 C or below 0 C and or with high non condensing humidity above 90 for maintaining the battery l...

Page 5: ...ies are promptly supplying current to the inverter Then after passing through the wave filter the power can be sent to user s equipment without interruption 2 4 Power supply by bypass The bypass mode only happens in the following conditions 1 overload 2 UPS failure 3 Switch on keep pressing the ON button for 3 seconds the UPS will be in process of soft starting within 15 seconds 4 Switch off keep ...

Page 6: ...nging frequency 5 times per second when the batteries are nearly exhausted in order to remind the persons that the batteries are used up and that the UPS will soon cut out When the batteries are almost used up the UPS shuts down automatically to protect the batteries 3 4 Protective functions of the Online UPS Overload on main power condition if the load amounts more than 110 on mains condition the...

Page 7: ...ency 50Hz or 60Hz was before the mains collapsed 3 9 Battery detection The product can work with monitoring software to capture the battery at a certain time In the case of any error message such as an open circuit of battery cable or battery failure the unit can catch the error information through the communication ports to advise the user Meanwhile the UPS has a self protection function by shutt...

Page 8: ...t down within 5s Auto shut down with no load optional 5 shut down within 1min Short circuit System shuts down automatically Alarm AC abnormal Once per 4s silent after 40s Battery low Once per 0 2s Overload Once per 1s Battery DC voltage 24V 24V 36V 48V H 48V configuration standard UPS 2 x 12V7Ah 2 x 12V8Ah 3 x 12V8Ah 4 x 12V8Ah Recharge time 90 capacity after 8 hours Charging current long backup 1...

Page 9: ...when the UPS is working 4 UPS working condition indicator the green light is on when there is main power input the red light is on when there is no mains flowing 5 AC indicator orange the light is on when there is input main power 6 ON starting button start the UPS by pressing the button for 3 seconds The UPS produces output power normally within 15 seconds when starting daily 7 OFF shut down butt...

Page 10: ...n on the front panel for 3 seconds The UPS switches to bypass mode when the mains in on In this moment the bypass LED is illuminated otherwise the UPS shuts down its operating Precautions 1 When starting the computer take care of starting first the UPS and only after then the load of the computer And when switching off turn off first the computer and afterwards the UPS 2 Normally it s not necessar...

Page 11: ...utput power Then cut the main power supply off The UPS transfers automatically to battery mode before shutting down Take note of the discharging time in order to refer it later The total of the load current consumption is calculated in the unit Watt If the marking on the UPS just shows the power capacity in the unit VA then multiply the VA rating with the power factor PF 0 6 for calculating the ra...

Page 12: ...cannot work Whether the battery is not charged or the UPS is not switched on When power has failing computer stops to work Start the UPS when mains is normal Charge the battery during more than 10 hours and then start the UPS When the mains is connected the UPS beeps for 60 seconds and transfers then to bypass When no main power is entering the UPS shuts itself down automatically after 60 seconds ...