background image

Vision™ OPLC™ V290-19-C30B, V290-19-T40B

8

Unitronics 

CANbus

These controllers comprise a CANbus port. Use 
this to create a decentralized control network of 
up to 63 controllers, using either Unitronics’ 
proprietary CANbus protocol or CANopen. 
The CANbus port is galvanically isolated. 

CANbus Wiring 

Use twisted-pair cable. DeviceNet® thick 
shielded twisted pair cable is recommended. 

Network terminators: These are supplied with the 
controller. Place terminators at each end of the 
CANbus network.  
Resistance must be set to 1%, 121

Q

, 1/4W. 

Connect ground signal to the earth at only one 
point, near the power supply. 

The network power supply need not be at the 
end of the network 

CANbus Connector 

121

terminating

resistor

121

terminating

resistor

Circuit
protection
device

+

-

24V Power

Supply

-V

L

H

+V

PE

-V

L

H

+V

PE

-V

L

H

+V

PE

The information in this document reflects products at the date of printing. Unitronics reserves the right, subject to all applicable laws, at any time, at its sole 

discretion, and without notice, to discontinue or change the features, designs, materials and other specifications of its products, and to either permanently or 

temporarily withdraw any of the forgoing from the market. 
All information in this document is provided "as is" without warranty of any kind, either expressed or implied, including but not limited to any implied warranties of 

merchantability, fitness for a particular purpose, or non-infringement. Unitronics assumes no responsibility for errors or omissions in the information presented in 

this document. In no event shall Unitronics be liable for any special, incidental, indirect or consequential damages of any kind, or any damages whatsoever arising 

out of or in connection with the use or performance of this information. 
The tradenames, trademarks, logos and service marks presented in this document, including their design, are the property of Unitronics (1989) (R"G) Ltd. or other 

third parties and you are not permitted to use them without the prior written consent of Unitronics or such third party as may own them.

 

11/06 DIG-V290-CT

 

Summary of Contents for OPLC V290

Page 1: ...ules Plug into the back of the controller to provide an on board I O configuration I O Expansion Modules Via adapter use up to 8 I O Expansion Modules comprising up to 128 additional I Os Programming Write both the HMI and Ladder control application using VisiLogic freeware The Vision User Guide and the product s technical specification sheet contain additional information These documents are loca...

Page 2: ...r property damage Do not attempt to use this device with parameters that exceed permissible levels To avoid damaging the system do not connect disconnect the device when power is on Environmental Considerations Do not install in areas with excessive or conductive dust corrosive or flammable gas moisture or rain excessive heat regular impact shocks or excessive vibration in accordance with the stan...

Page 3: ...Dimensions 2 If you mount the controller on a metal panel earth the power supply a Bore a hole to suit the NC6 32 screw supplied with the kit b Scrape panel paint away from the contact area to ensure a conductive connection c Drive the screw into the hole d Place the following hardware screw s shank in the order shown in the accompanying figure washer ring cable shoe second washer spring and nut N...

Page 4: ... and I O Expansion Modules Installation instructions and other data may be found in the module s technical specification sheet Wiring General Do not touch live wires Unused pins should not be connected Ignoring this directive may damage the device Caution To avoid damaging the wire do not exceed a maximum torque of 0 5 N m 5 kgf cm Do not use tin solder or any substance on stripped wire that might...

Page 5: ...ections Caution Signals are related to the controller s 0V the same 0V is used by the power supply Always use the appropriate port adapters Serial Communications The serial ports are type RJ 11 and may be set to either RS232 or RS485 via DIP switches in accordance with to the table shown on page 7 Use RS232 to download programs from a PC and to communicate with serial devices and applications such...

Page 6: ...tons on the sides of the controller two on either side 2 Press the buttons and hold them down to open the locking mechanism 3 Gently rock the module from side to side easing the module from the controller Opening and Closing the Controller 1 Locate the slots on the sides of the controller 2 Open the controller by inserting a flat bladed screwdriver into the slots located on the side of the control...

Page 7: ...even pressure on all 4 corners until you hear a distinct click The module is now installed Check that all sides and corners are correctly aligned RS232 RS485 DIP Switch Settings Switch Settings 1 2 3 4 5 6 RS232 ON ON ON OFF ON OFF RS485 OFF OFF OFF ON OFF ON RS485 with termination ON ON OFF ON OFF ON Default factory setting Causes the unit to function as an end unit in an RS485 network ...

Page 8: ... all applicable laws at any time at its sole discretion and without notice to discontinue or change the features designs materials and other specifications of its products and to either permanently or temporarily withdraw any of the forgoing from the market All information in this document is provided as is without warranty of any kind either expressed or implied including but not limited to any i...

Reviews: