background image

2

DE3642

A.

Connect the snap-on battery clip to the battery terminals. 

The

clip will not fit if the contacts are reversed, but take care

not to make a prolonged reverse contact - the battery will

discharge rapidly through the built in protection diode!

 

Note:

 When the battery first makes contact, the alarm horn may

sound for one second. This indicates that the battery is

connected properly.

B.

Push the battery firmly in until it is seated tightly within the

holder, with the snap-on clip pressed against the contact

springs.

C.

Close the cover, then press the test button for about 5

seconds until the horn sounds two sequences of a loud

3-beep alarm. 

This means that the smoke detection

section is working properly.

2.5 Resetting the Transmitter Module

and Enrolling its PowerCode ID

A rear tamper protection switch is

mounted under the PC  board.

The tamper switch actuator,

extending through a hole in the

base (see Figure 4), is pressed

against the bracket when the unit

is attached to the bracket.
Removal of the unit from the

bracket will cause the switch

contacts to open, creating a

tamper event, which will be

reported by the transmitter to the

control panel.

Battery cover 

Figure 4.

 Rear Tamper

Refer to the control panel’s installation instructions and follow the

procedure given there for enrolling transmitter IDs in the control

panel's memory. When required to initiate a transmission for

enrollment, press the smoke detector’s test button until the built-in

horn sounds, or press the tamper switch.

Note:

 It is much easier to carry out this operation while holding

the MCT-425 in your hand, close to the control panel.

2.6 Mounting the Bracket in Place

Read Section 4 in this manual first, then decide where to install a
detector. Refer to Figures 5 and 6 and proceed as follows:

Figure 5. 

Aligning the Bracket

Figure 6. 

Mounting the Bracket

  A . 

At the location where you intend to install the detector, draw a
horizontal line six inches long.

  B . 

Remove the mounting bracket from your unit by rotating it
counterclockwise (see Figure 2).

C.

Place the bracket so that the two longest hole slots are

aligned on the line. in each of the keyhole slots, draw a mark
to locate a mounting plug and screw as in Figure 5.

D.

Remove the bracket.

E.

Using the appropriate size drill, drill two holes at the marks

and insert wall plugs.

F.

Using the two screws and wall plugs (all supplied), attach the

bracket to the wall (see Figure 6).

2.7 Final Assembly and Test

Note:

 Unauthorized removal of the unit from the bracket will

initiate a tamper alert!

A.

Press the test button until the built-in horn sounds. Verify that

the transmitted signal has been received at the control panel,
and that the control panel responds accordingly by activating
the fire alarm siren or any other warning device.

B.

Attach the detector to the bracket as shown in Figure 7. Pull

outward to make sure that the detector is securely attached to
the bracket.

Note:

 A battery must be inserted into the detector before the

detector can be mounted onto the bracket.

Figure 7.

 Final Assembly

3

33

3. SPECIFICATIONS

. SPECIFICATIONS

. SPECIFICATIONS

. SPECIFICATIONS

SMOKE DETECTOR
Detection Sensitivity:

 2.66 ±1.11 %/ft obscuration

Alarm Sound Level:

 85 dB at 3 m (10 feet)

TRANSMITTER AND CODING
Operating Frequency (MHz):

 315, 433.92, 868.95, 869.2625 or

other frequency according to local requirements.

Transmitter's ID Code:

 24-bit digital word, over 16 million

combinations, pulse width modulation.

Overall Message Length:

 36 bits

Supervision:

 Automatic signaling at 60-minute intervals (US

version), 15-minute interval (UK version) or according to the local
standards.

Tamper Alerts: 

Tamper event (removal of the unit from its bracket)

is reported once, until the tamper switch is restored.

Transmission Indicator: 

Yellow LED lights upon transmission

(visible only when Switch SW-1 is ON).

ELECTRICAL DATA
Power Source:

 9 Volt alkaline or lithium.

Operation Voltage:

 From 7.2 V to 9.5 V.

Current Drain: 

28 µA standby, 20 mA in operation

Battery Life Expectancy:
Alkaline:

 at least 1 year (for typical use)

Lithium: 

at least 2 years (for typical use)

Battery Supervision:

 Automatic transmission of battery status

data as part of any transmitted message.

Audible Low Battery Warning: 

Built-in horn beeps once a

minute for

 

up to 30 days when the battery voltage drops.

PHYSICAL DATA
Operating Temperature:

 0

°

C to 37.8

°

C (32

°

F to 100

°

F).

Relative Humidity:

 10% to 85%

Dimensions:

 130 mm (5.12") x 75 mm (2.95")

Weight (including battery):

 272 g (9.6 oz)

Attach to

Bracket

Rotate

Clockwise

TAMPER SWITCH ACTUATOR

Align Tabs

With Slots

BRACKET

DETECTOR

Summary of Contents for MCT-425

Page 1: ...r fire protection in buildings not defined as households WARNING This detector if used as a stand alone unit will not alert people who are hard of hearing 2 2 2 2 INSTALLATION SUMMARY INSTALLATION SUMMARY INSTALLATION SUMMARY INSTALLATION SUMMARY 2 1 Disassembly Separate the unit from its mounting bracket as shown in Figure 2 Figure 2 Separating the MCT 425 from its Bracket 2 2 Setting the Functio...

Page 2: ... mounting plug and screw as in Figure 5 D Remove the bracket E Using the appropriate size drill drill two holes at the marks and insert wall plugs F Using the two screws and wall plugs all supplied attach the bracket to the wall see Figure 6 2 7 Final Assembly and Test Note Unauthorized removal of the unit from the bracket will initiate a tamper alert A Press the test button until the built in hor...

Page 3: ...e 12 Recommended Location to Mount Smoke Detectors in Rooms with Sloped Gabled or Peaked Ceiling CAUTION As required by the California State Fire Marshall Early warning fire detection is best achieved by the installation of fire detection equipment in all rooms and areas of the household as follows 1 A smoke detector installed in each separate sleeping area in the vicinity but outside the bedrooms...

Page 4: ... false alarms Install smoke detectors at least 1 5 meters 5 feet from such lights Figure 13 Recommended Smoke Detector Locations to Avoid Air Streams with Combustion Particles WARNING Never remove batteries to stop a false alarm Open a window or fan the air around the detector to get rid of the smoke The alarm will turn itself off when the smoke is gone If false alarms persist attempt to clean the...

Page 5: ...to leave the home by themselves if necessary Show them how to check to see if doors are hot before opening them Show them how to stay close to the floor and crawl if necessary Show them how to use the alternate exit if the door is hot and should not be opened Decide on a meeting place which has a safe distance from your house Make sure that all your children understand that they should go and wait...

Page 6: ...heir own warranty if any The Manufacturer shall not be liable for any damage or loss whatsoever whether directly indirectly incidentally consequentially or otherwise caused by the malfunction of the Product due to products accessories or attachments of others including batteries used in conjunction with the Products The Manufacturer does not represent that its Product may not be compromised and or...

Reviews: