background image

D-300767 

4.3 Connection of flood Sensor's cable 

to the Flood Detector 

Connect the 2 sensor's wires to the AUX terminals of the MCT-560 flood 
detector (see figure 4). Either one of the wires may be connected to either 
terminal. 

4.4 Detector Closure 

Close the detector (refer to figure 3). 

Not e:   Flood sen sor height
according to required flood
detection. Recommended 0-3cm
from floor.

FLOOD

DETECTOR

FLOOD
SENSOR
CABLE

2 - 3 m

(recommended

length)

WATER

FLOOD
SENSOR

 

Figure 2 

Flood Sensor Installation 

 

2

4

3

1

Remove
screw

Press the flexible
catch and remove
the printed circuit

Mark and drill 2 holes in mounting
surface and fix the base to the wall
with 2 countersunk head screws

Separate
the base

 

Figure 3 

Flood Detector Installation 

 

FUNCTION SELECTOR

TRANSMITTER

RF MODULE

TAMPER

SWITCH

AUX. INPUT

TERMINALS

3 V LITHIUM BATTERY

LED

FLEXIBLE RETAINER

P.C. BOARD

SUPPORTS

WIRES TO FLOOD

SENSOR

 

Figure 4 - Flood Detector Printed Circuit Board 

 
Note regarding flood detector internal function selector 
The flood detector has 4 internal switches (see Fig. 4): 
SW1 and SW2: These switches must be always in OFF (as set 
by the manufacturer). 
SW3: If the detector will be used only with MCW-570, the position 
of this switch is not important. If the detector will be used with 
other systems (e.g. PowerMax), this switch enables (ON) or 
disables (OFF) event end reporting. 
SW4: This switch is not used. 

 

5. CONTROL UNIT INSTALLATION 

5.1 Installation Location 

The Control Unit, the flood detectors and the flood sensors are designed 
for installation inside the house only. The electro-mechanical water 
valve(s) should be installed on the site main water pipe. 

5.2 Control Unit Installation 

(see figure 5)

 

Before installation, disconnect the power that was connected to the 
Control Unit during the enrolling process. Install the Control Unit as shown 
in figure 5, step 3. at height of at least 1.2m. 

Snap-in

tooth

(1 of 2)

Base

Cover

CLOSED LED (red)

READY LED (green)

Remove

 screw

Push near the 2
snap-in teeth to

remove the cover

2

1

Wire

 antenna

Close cover

and fasten

with screw

4

3

Hold the base on mounting
surface, mark and drill 2
holes in mounting surface,
i n s e r t   w a ll   a n c ho r s   i f
necessay and enter wires
into the base through the
w ir i ng  ho l es  o r   w ir i n g
knockouts. Attach the base
to the mounting surface with
two screws.

 

Figure 5 - Control Unit Mounting

 

5.3 Electro-mechanical Valve Installation 

The water valve(s) must be installed by a qualified plumber in the site 
main water pipe. 
Caution: The water valve(s) must be installed in addition to the existing 
water valve and not instead of it!
 

5.4 Power Connection 

Connect the AC adaptor output (9VAC), that is supplied with the system, 
to the "PWR" terminals (see figure 6) - disregard the polarity. 

RELAY

N.C.

N.O. C

9VAC

Water

valve

A

Water

valve

B

Closed

LED

(red)

Ready

LED

(green)

CONTROL

MODULE

RECEIVER

MODULE

Signal / memory
status red LED

Memory

location

yellow

LED

Delete
button

Tamper

switch

Close

button

Open

button

operate

learn

toggle

pulse

Jumpers

 

Figure. 6 - Power Connection

 

5.5 One Water Valve Wiring 

Connect the water valve cable to VALVE A or VALVE B connector (see 
Fig. 6).  

5.6 Two Water Valves Wiring 

Connect the cable of one valve to VALVE A connector and the cable of 
the other valve to VALVE B connector. 

5.7 Remote control Panel Wiring 

(option)

  

Perform wiring as shown in figure 7.  

RELAY

N.C.

N.O. C

FLOOD

ZONE

GND

TRANSMITTER

INACTIVITY

INPUT

OPTIONAL REMOTE CONTROL PANEL

LOW

BAT

INPUT

+Vcc

18

Ω

18

Ω

+Vcc

Notes
The ZONE INPUT is
activated when flood occurs.

The TRANSMITTER
INACTIVITY INPUT
 is
activated if a supervised flood
detector fails to send its
attendance message within
a 4-8 hours time frame.

The LOW BAT INPUT is
activated whenever a low
battery message is received
from one of the flood
detectors.

REL AY

N.C.

N.O . C

MCW-570

CONTROL

UNIT

 

Figure 7 - Optional Remote Control Panel Wiring 

5.8 Final Actions 

Carefully close the front panel of the control panel, straighten the antenna wire 
and tighten the front panel with the screw (see figure 5). 

 

Summary of Contents for MCW-570

Page 1: ... visible only after removal of the Control Unit cover Red SIGNAL MEMORY STATUS LED illuminates as long as the receiver receives signal from recognized flood detector This LED is also used during the flood detectors learning process described in par 3 3 Yellow MEMORY LOCATION STATUS LED indicator used during the learning process 2 SPECIFICATIONS 2 1 Control Unit Specifications RF SECTION Front End ...

Page 2: ...w the status of the selected location as follows Memory Status Red LED Response Location is free LED Flashes Location already contains an ID LED Lights steadily C If the memory status is free as shown in the above table initiate a transmission from the flood detector you wish to enroll in the selected location by inserting battery into the flood detector or if it s battery was already inserted cli...

Page 3: ...Base Cover CLOSED LED red READY LED green Remove screw Push near the 2 snap in teeth to remove the cover 2 1 Wire antenna Close cover and fasten with screw 4 3 Hold the base on mounting surface mark and drill 2 holes in mounting surface insert wall anchors if necessay and enter wires into the base through the wiring holes or wiring knockouts Attach the base to the mounting surface with two screws ...

Page 4: ...ot covered by this Warranty The Manufacturer does not represent that this Product may not be compromised and or circumvented or that the Product will prevent any death and or personal injury and or damage to property resulting from burglary robbery fire or otherwise or that the Product will in all cases provide adequate warning or protection The Product properly installed and maintained only reduc...

Reviews: