REVIEWING TROUBLES AND ALARM MEMORY
16
D-307503 PowerMaster 360 User's Guide
Correcting trouble conditions
The trouble indicator and flashing TRBL message are cleared after you eliminate the cause of fault. The table
below describes the system faults and corresponding actions to take to resolve the problem.
If you do not
know how to correct a trouble situation, report it to your installer and seek their advice.
Fault
What it means
1-WAY
The device functions but cannot "hear" the panel. The control panel cannot
configure or control the device. Battery consumption increases.
AC FAILURE
There is no power supplied to the device.
CLEAN ME
The fire detector must be cleaned
COMM. FAILURE
A message could not be sent to the monitoring station or to a private telephone (or
a message was sent but was not acknowledged)
CPU LOW BATTERY
The backup battery within the control panel is weak and must be replaced (see
Chapter 8. Maintenance, "Replacing Backup Battery").
CPU TAMPER OPEN
The control panel was physically tampered with or its cover was opened, or it was
removed from wall.
GAS TROUBLE
Gas detector failure
GSM NET FAIL
The GSM communicator is not able to connect to the cellular network.
JAMMING
A radio-frequency signal which is blocking all communication frequency channels
between the sensors and control panel is detected.
LINE FAILURE
There is a problem with the telephone line
LOW BATTERY
The battery of the indicated device is near the end of its useful life.
MISSING
A device or detector has not reported for some time to the control panel.
NOT NETWORKED
A device was not installed or not installed correctly, or, cannot establish
communication with the control panel after installation.
RSSI LOW
The GSM communicator has detected that GSM network signal is weak
SIREN AC FAILURE
There is no power to the siren
TAMPER OPEN
The sensor has an open tamper
TROUBLE
The sensor reports trouble
SOAK TEST FAIL
Detector alarms when in Soak Test mode