Air Handler
13
Notes:
1) For air handler without installing electric heater, connect the power cord to “L1” and “L2” on
terminal board.
2) For air handler with electric heater, connect the power cord to circuit breaker. If the heat kit
without circuit breaker, connect the power cord to the stripped black and red wires.
3) Remove the black lead from "X7" terminal on the main board and then connect the blue lead
to "X7" terminal for 208 volts, taping the unused black lead.
4) 90 seconds off delay when "G" is de-energized.
5) Jumper "R" and "O" together if working with cooling only condensing unit.
7.6 Thermostat Wiring
INDOOR UNIT
OUTDOOR UNI
T
WIRED-CONTROLLER
Figure 4
8. Refrigerant Pipe
WARNING
WHEN WELDING ON THE PAINTED SURFACES OF THE UNIT, QUENCHING CLOTH IS
STRONGLY ADVISED TO PREVENT SCORCHING OR DAMAGING THE UNIT SURFACES.
SOLDER WITH A MINIMUM OF 5% SILVER IS RECOMMENDED.
WARNING
THIS PRODUCT IS FACTORY-SHIPPED UNDER PRESSURE. FOLLOW THESE
INSTRUCTIONS TO PREVENT INJURY.
8.1 Piping Preparation
All cut ends are to be round, burr free, and cleaned. Failure to follow this practice increases the
chances for refrigerant leakage.
After Brazing
Quench all welded joints with water or a wet rag.
Piping Size
For the correct piping size, follow the specification for the condenser/heat pump.