To extend the life of the stabilizer keep it clean. Unplug a voltage regulator
when you need to clean it. Don't allow water to damage a voltage regulator.
Keep it away from water and dampness.
When you switch the device off and when you don't use it for a long time,
disconnect the power cord from the outlet.
Keep a voltage regulator in a dry and airy place far from children.
ATTENTION
!
Use a voltage regulator only for the purpose intended
Use a voltage regulator only with the grounding .
It's forbidden to use a voltage regulator in places with
high humidity, in explosible buildings and in
chemically active media, which can destroy metals and
isolation.
It's forbidden to dismantle a voltage regulator and
operate it with the removed housing.
It's forbidden to close the vents when a voltage
regulator is switched on
WARNING!
Do not cover a voltage regulator with towels, blankets or
covers, don't put it close to a wall or other equipment. All
above mentioned can reduce the efficiency of the ventilation
system, it can cause overheating and disconnection of a
voltage regulator.
Carefully remove the stabilizer from the packaging. Remove the foam
seals and remove the plastic cover. Packaging save for its further use in the
case of long-term storage.
Install the stabilizer on a flat, horizontal surface. Minimal distance to the
wall should be at least 0.5 m to ensure efficient cooling.
Unscrew the screws of the terminal panel (see Fig. 1) and remove the
panel from the chassis of the stabilizer. Connect the grounding wire and input
supply network, reliably securing them in the nests of the appropriate
terminals.
To select a cross-section of connecting wires
use of data from the table
below.
OPERATING
4
ATTENTION
!
Choose to connect the regulator to the power supply
network and for connection of consumers to the stabiliser
wire, calculated on the load of not less than the maximum
allowable for the given model of the stabilizer.
The power of the
connected devices, W
M
in
imum cross-section (not less
than)
of the
copper cable
connection
,
sq.mm
1 000
1,0
1 500
1,5
2 000
2,0
3 000
4,0
5 000
4,0
8 000
6,0
10 000
6,0