95x Series Operating Manual - May 17, 2022
Page
137
of
155
5
<NR3>
Dwell time (in seconds)
<EMPTY>
Step is to be user terminated
6
<NR3>
Pre-check delay (in seconds)
7
<STRING>
AMPS - Leakage limits are in Amps
OHMS - Leakage limits are in
Ω
8
<NR3>
Minimum Leakage Limit (in A or
Ω
)
9
<NR3>
Maximum Leakage Limit (in A or
Ω
)
<EMPTY>
No maximum limit (only valid for impedance)
10
<NR1>
Time period for arc detection (4, 10, 15, 20, 30 or 40)
<EMPTY>
Arc detection disabled
11
<NR1>
Arc detection limit (in mA)
<EMPTY>
Only valid if arc detection disabled in field 10
12
<STRING>
NONE - No discharge if next step compatible
FAST - Fast discharge
RAMP - Discharge same as ramp
13
<STRING>
ABORT - Abort on failure
CONT - Continue on failure
14
<NR3>
Min Load (in Farads), may be <MISSING> if field 15 is also <MISSING>
15
<EMPTY>
Load is not grounded
<MISSING>
<STRING>
GND : Load is grounded (only valid if option HSS or HSS-2 is fitted)
ISO : Load is not grounded
Example
–
ADD,DCW,1000.0,0.015,1.5,60.0,0.0,AMPS,0.0,25e-6,4,10,FAST,ABORT
Configures the following (in order)
–
A DCW type test step
1000V test voltage
15mA breakdown limit
1.5 second ramp time
60 second dwell time
0 second delay
Define leakage limits in Amps
No minimum leakage current limit
25uA maximum leakage current limit
4us arc detection time
10mA arc detection limit
Fast discharge
Abort test sequence if fails
Minimum load during ramp is set to 0 since both fields 14 and 15 are missing
DUT is isolated since both fields 14 and 15 are missing
DCIR CONFIGURATION FIELDS
Field # Field Format Value
1
<STRING>
DCIR
2
<NR3>
Test Voltage (in V)