56
2553/ 2553E Command Guide
Defining Current Measurement Results
AMPS[
phase
/CF]
The Crest Factor of the current input signal, using either AC or DC coupling. (See the
AC-ONLY command.) The result format is floating point, unitless, and is always
positive. TOTAL data is derived from the highest phase peak and the mean phase RMS
values.
AMPS[
phase
/DC]
The mean amplitude of the current input signal. If configured as AC only then this result
is always zero. (See the AC-ONLY command.) The result format is floating point, in
Amps. TOTAL data is the mean for all phases.
AMPS[
phase
/FUND]
The RMS current amplitude measurement result evaluated for the fundamental
component only. The result format is floating point, in Amps, and is always positive.
TOTAL data is the mean for all phases.
AMPS[
phase
/PEAK]
The highest absolute peak measured instantaneous current amplitude. The result format
is floating point, in Amps, and is always positive. TOTAL data is derived from the
highest phase peak.
AMPS[
phase
/RMS]
The RMS current amplitude measurement result, including DC if configured (see the AC-
ONLY command), over the full configured bandwidth (see the BANDWIDTH
command), including any non-harmonic content. The result format is floating point, in
Amps, and is always positive. TOTAL data is the mean for all phases.
AMPS[
phase
/THD]
The ratio of the harmonic current amplitude of all harmonics except the fundamental, to
the current fundamental. The result format is floating point, in percent, and is always
positive. TOTAL data is the mean for all phases.
AMPS[
phase
/
harmonic
]
The RMS current amplitude measurement result evaluated at the specified harmonic. The
result format is floating point, in Amps, and is always positive. TOTAL data is the mean
for all phases.
Summary of Contents for Xitron 2553
Page 1: ...IEEE488 COMMAND GUIDE 2553 2553E Three Phase Power Analyser ...
Page 2: ......
Page 10: ...10 2553 2553E Command Guide ...
Page 38: ...38 2553 2553E Command Guide ...