Reading Measurement Results from the 2553/ 2553E
59
Defining Voltage Measurement Results
VOLTS[
phase
/CF]
The Crest Factor of the voltage input signal, using either AC or DC coupling. (See the
AC-ONLY command.) The result format is floating point, unitless, and is always
positive. TOTAL data is derived from the highest phase peak and the mean phase RMS
values.
VOLTS[
phase
/DC]
The mean amplitude of the voltage input signal. If configured as AC only then this result
is always zero. (See the AC-ONLY command.) The result format is floating point, in
Volts. TOTAL data is the mean for all phases.
VOLTS[
phase
/FUND]
The RMS voltage amplitude measurement result evaluated for the fundamental
component only. The result format is floating point, in Volts, and is always positive.
TOTAL data is the mean for all phases.
VOLTS[
phase
/PEAK]
The highest modulus peak measured instantaneous voltage amplitude. The result format
is floating point, in Volts, and is always positive. TOTAL data is derived from the highest
phase value.
VOLTS[
phase
/RMS]
The RMS voltage amplitude measurement result, including DC if configured (see the
AC-ONLY command), over the full configured bandwidth (see the BANDWIDTH
command), including any non-harmonic content. The result format is floating point, in
Volts, and is always positive. TOTAL data is the mean for all phases.
VOLTS[
phase
/THD]
The ratio of the harmonic voltage amplitude of all harmonics except the fundamental, to
the voltage fundamental. The result format is floating point, in percent, and is always
positive. TOTAL data is the mean for all phases.
VOLTS[
phase
/
harmonic
]
The RMS voltage amplitude measurement result evaluated at the specified harmonic. The
result format is floating point, in Volts, and is always positive. TOTAL data is the mean
for all phases.