background image

Wiring Diagrams

Wiring Diagrams

Tech Settings

Typical 1H/1C System: 1 Transformer

Typical 1H/1C System: 2 Transformer

Typical 1H/1C Heat Pump System

COMPRESSOR

RELAY

FAN RELAY

COOL CHANGE

OVER VALVE

HEAT CHANGE

OVER VALVE

O

B

C

R

L2

L1

(HOT)

RC
RH

Y
C

W

G

Power supply

Factory-installed jumper.  Remove only when installing on 2-transformer systems

Use either O or B terminals for changeover valve

Use a small piece of wire (not supplied) to connect W and Y terminals

Set fan operation setting to Electric

Optional 24 VAC common connection when thermostat is used in battery power mode

Typical Heat-Only System

Typical Heat Only System With Fan

Typical Cool-Only System

HEAT RELAY

RC
RH

Y
C

W

G

C

R

L2

L1

(HOT)

FAN RELAY

HEAT RELAY

RC
RH

Y
C

W

G

C

R

L2

L1

(HOT)

FAN RELAY

COMPRESSOR 

RELAY

C

R

L2

L1

(HOT)

RC

RH

Y
C

W

G

This thermostat has a technician setup menu for easy installer 

configuration. To setup the thermostat for your particular application:

Swing Setting Tip

Temperature swing, sometimes called differential or cycle rate, can be customized 

for this individual application.  For most applications choose a swing setting that is 

as long as possible without making the occupants uncomfortable.

Technician Setup Menu

1. To enter all other steps press and hold           and            buttons 

     together for 3 seconds. This 3 second delay is designed so that 

     homeowners do not accidentally access the installer settings.

2. Use            and             buttons to set.

3. Press the Program button to advance to the next step. 

4. Press the time button to go back to the previous stop.

5. Press the Hold/Run button to exit.

Tech Settings

COMPRESSOR

RELAY

FAN RELAY

HEAT RELAY

RC
RH

Y
C

W

G

C

R

L2

L1

(HOT)

RC

RH

Y

C

W

G

COMPRESSOR

RELAY

HEAT RELAY

FAN RELAY

L2

L1

(HOT)

L2

L1

(HOT)

C

R

C

R

REMOVE JUMPER

The Technician Setup Menu

LCD Will Show

The compressor short cycle delay 

protects the compressor from 

short cycling. This feature will not 

allow the compressor to be turned 

on for 5 minutes after it was last 

turned off.

Selecting “ON” will not allow 

the compressor to be turned on 

for 5 minutes after the last time 

the compressor was switched 

off. Select “OFF” to remove this 

delay.

0

This feature allows the installer 

to change the calibration of the 

room temperature display. For 

example, if the thermostat reads 

70˚ degrees and you would like it 

to read 72˚ then 2.

Room 

Temperature 

Calibration

You can adjust the room 

temperature display to read 

4˚above or below the factory 

calibrated reading.

Tech Settings

Adjustment Options

Compressor

Short Cycle

Delay

Default

0N

Cd

0

Next Step

Prev Step

CAL

Next Step

Prev Step

0.5

The swing setting often called 

“cycle rate”, “differential” or “ 

anticipation” is adjustable.  A 

smaller swing setting will cause 

more frequent cycles and a larger 

swing setting will cause fewer 

cycles.

Cooling 

Swing

The cooling swing setting is 

adjustable from 0.2˚ to 2˚.  For 

example: A swing setting of 

0.5˚ will turn the cooling on at 

approximately 0.5˚ above the 

setpoint and turn the cooling 

off at approximately 0.5˚ below 

the setpoint.

05

Next Step

Prev Step

The swing setting often called 

“cycle rate”, “differential” or “antic-

ipation” is adjustable.  A smaller 

swing setting will cause more 

frequent cycles and a larger swing 

setting will cause fewer cycles.

The heating swing setting is 

adjustable from 0.2˚ to 2˚. For 

example: A swing setting of 

0.5˚ will turn the heating on at 

approximately 0.5˚ below the 

setpoint and turn the heating 

off at approximately 0.5˚ above 

the setpoint.

Heating

 Swing

0.4

04

Next Step

Prev Step

This feature allows you to set a 

maximum heat setpoint value. The 

setpoint temperature cannot be 

raised above this value.

Heating 

Setpoint

Limit

90

Use the         and          key to 

select the maximum heat 

setpoint.

Next Step

Prev Step

HE L

dFHE

Select F for Fahenheit temperature 

read out or select C for Celsius 

read out.

F for Fahrenheit

C for Celsius

F or C

F

F

FC

Next Step

Prev Step

This feature allows you to set a 

minimum cool setpoint value. The 

setpoint temperature cannot be 

lowered below this value.

Cooling 

Setpoint

Limit

44

Use the         and          key to 

select the minimum cool 

setpoint.

Next Step

Prev Step

CO L

LCD Will Show

Tech Settings

Adjustment Options

Default

You can configure this thermo-

stat to have 7 Day or 5+1+1 

programming.

Program

Options

5d

Use the         and          key to 

select 

7d

 for 7 Day or 

5d

 for 

5+1+1 programmable.

Next Step

Prev Step

This feature will start heating early 

to bring the building temperature 

to its programmed setpoint by the 

beginning of the WAKE, OCCUPIED 

time period. 

Morning 

Recovery

ON

Use the         or         key to 

turn on or off.

MORN RECOV

Reviews: