Thermostat Quick Reference
4
5
Thermostat Quick Reference
The low battery icon is displayed when the AA battery power is low. Whenever the
thermostat detects low battery voltage from the AA batteries, the low battery icon
will begin flashing on the screen for 21 days (if the batteries are not changed). If the
batteries are not changed 22 days after the thermostat detects low battery voltage, the
thermostat screen will only show the flashing battery icon until buttons are pressed. If
the batteries are not changed 43 days after the thermostat detects low battery voltage,
the thermostat screen will only show the flashing battery icon until buttons are pressed
and the set points will offset to 85°F/29°C in cooling and 55°F/13°C in heating. At this
stage, set point changes can be made temporarily but, the set points will change back
to defaulted values after a 4-hour period. The thermostat will continue to perform this
low battery flashing, temperature offset condition until the internal voltage threshold
is reached. When the thermostat internal voltage threshold is reached, all relays will be
opened and the thermostat will become inoperable until new batteries are installed.
Important:
Battery Door Information
Use the finger bevel on
the lower portion of the
thermostat to open the
easy access battery door.
Replace with
2 AA Alkaline
Batteries. High
quality Alkaline
batteries are
recommended.
Simple operating instructions are
found on the back of the battery door.
Set At
COOL ON
WAKE
Sun Mon Tue Wed Thu Fri Sat
EmHEAT ON
STAGE 1&2
LEAVE
RETURNSLEEP
AMPM
HOLD
Indicates the current room temperature
Time and day of the week
Setpoint:
Displays the user selectable setpoint temperature.
Hold
is displayed when the thermostat program is permanently overridden.
System Operation Indicators:
The COOL ON, HEAT ON will display when COOL or HEAT is on.
Note: The Compressor delay feature is active if these are flashing.
Low Battery Indicator:
Replace batteries when this indicator is shown.
Program Time Periods:
This thermostat has 4 programmable time periods
per day.
Stages:
Indicates the stages of heat that are active.
1
2
3
7
8
1
3
2
7
8