background image

Wiring 

Wiring 

Terminal Designations on the Base Module

This thermostat is shipped from the factory to operate a conventional heating

and cooling system. This thermostat may also be configured for a heat pump 

system. See the “heat pump” configuration step on page 23 of this manual to 

configure the thermostat for heat pump applications.

Terminal

2 Heat 2 Cool

Conventional 

System

2 Heat 2 Cool

Heat Pump 

System

 3 Heat 2 Cool

Heat Pump 

System

RC

RH

C
B

O
G

W/E

Y

Y2

W2

Transformer power

(cooling)

Transformer power

(heating)

Transformer common

Energized in heating

Energized in cooling

Fan relay

First stage of heat

First stage of cool

Second stage of cool

Second stage of heat

Transformer power

(cooling)

Transformer power

(heating)

Transformer common

Heat pump changeover 

valve energized in heating

Fan relay

First stage of 

emergency heat

First stage of heat & cool

Second stage of cool

Auxiliary heat relay,

second stage of heat

Heat pump changeover 

valve energized in cooling

Transformer power

(cooling)

Transformer power

(heating)

Transformer common

Heat pump changeover 

valve energized in heating

Fan relay

First stage of 

emergency heat

First stage of heat & cool

Second stage of cool 

& second stage of heat

Auxiliary heat relay,

third stage of heat

Heat pump changeover 

valve energized in cooling

Technician Setup

Technician Setup

H

Humidify

D

Humidify

Humidify

Dehumidify

Dehumidify

Dehumidify

Terminal

2 Heat 2 Cool

Conventional 

System

2 Heat 2 Cool

Heat Pump 

System

 3 Heat 2 Cool

Heat Pump 

System

If you add indoor or outdoor remote sensors to this wireless system 

you must hardwire the master thermostat.

Powering the Master Thermostat

Terminal Designations on the Master Thermostat

R

24 VAC transformer power

24 VAC 

transformer power

24 VAC

transformer power

C

transformer common

transformer common

transformer common

Typical 2H/2C System: 1 Transformer

Typical 3H/2C  or 2H/1C Heat Pump System

Power supply
Factory-installed jumper.  Remove only when installing on 2-transformer systems

Use either O or B terminals for changeover valve
If DEHUM relay requires a normally-energized input, set dehumidity relay to NC in 

technician setup.

RC
RH

Y
C

W/E

G

W2

Y2

COMPRESSOR

RELAY

FAN RELAY

AUXILIARY

HEAT

COMPRESSOR

RELAY 2

COOL CHANGE

OVER VALVE

HEAT CHANGE

OVER VALVE

C

R

L2

L1

(HOT)

RC
RH

Y
C

W/E

G

W2

Y2

COMPRESSOR

RELAY

FAN RELAY

HEAT RELAY 2

COMPRESSOR

RELAY 2

HEAT RELAY

C

R

L2

L1

(HOT)

O
B

This feature allows the installer 

to change the calibration of the 

room temperature display. For 

example, if the thermostat reads 

70˚ and you would like it to read 

72˚ then 2.

OFF

This feature will flash a reminder 

after the elapsed run time to 

remind the user to change the 

filter. A setting of  “OFF” will 

disable this feature.

Filter Change

Reminder

You can adjust the filter 

change reminder from “OFF” 

to 2000 hours of fan runtime 

in 50 hour increments.

Tech Setup Steps

Room

Temperature

Calibration

0˚F

This feature allows the installer 

to select the minimum run 

time for the compressor. For 

example, a setting of 4 will force 

the compressor to run for at 

least 4 minutes every time the 

compressor turns on, regardless 

of the room temperature.

You can set the minimum 

compressor run time to “OFF”, 

“3”, “4”, or “5” minutes. If 3,4 

or 5 is selected, the 

compressor will run for 

at least the selected time 

before turning off.

Minimum 

Compressor 

On Time

OFF

You can adjust the room 

temperature display to read 

up to 4˚above or below the 

factory calibrated reading.

Adjustment Options

Default

LCD Will Show

OFF

0

OFF

This thermostat has a technician setup menu for easy installer 

configuration. To set up the thermostat for your particular application:

1.  Press the 

MENU

 button.

2.  Press and hold the technician setup button for 3 seconds. This 3

      second delay is designed so that homeowners do not accidentally 

      access the  installer settings.

3. Configure the installer options as desired using the table below.

      Use the             or            keys to change settings and the next step

 

      

or previous step key to move from one step to another.  

Note:

 Only

      press the 

DONE

 key when you want to exit the  Technician Setup

      options.

4. Press the 

DONE

 key to exit.

Keypad Lockout Note:

 The selected keypad lockout functionality must 

be activated after exiting tech setup. If you do not perform this 

procedure, all keys will function freely. To lock the keypad hold down 

the        and        keys for 3 seconds.  You will see a lock in the display. To 

unlock the display hold down the         and         keys for 3 seconds.

CALIbRATE

The compressor short cycle delay 

protects the compressor from 

“short cycling”. This feature will 

not allow the compressor to be 

turned on for 5 minutes after it 

was last turned off.

Compressor

Short Cycle

Delay

ON

Selecting “ON” will not allow 

the compressor to be turned 

on for 5 minutes after the 

last time the compressor was 

on. Select “OF” to remove 

this delay.

CO

ON

OF

Tech Setup Steps

Adjustment Options

Default

LCD Will Show

Keypad 

Lockout

Keypad lockout allows you to 

configure the thermostat so that 

some or all of the keys don’t 

function.

PA= partial keypad lockout, 

which locks all the keys except 

the          or          keys.

FU= full keypad lockout, 

which locks out all the keys.

PA

See Keypad Lockout Note

PA

The swing setting often called 

“cycle rate”, “differential” or

“anticipation” is adjustable. A 

smaller swing setting will cause 

more frequent cycles and a larger 

swing setting will cause fewer 

cycles.

Cooling 

Swing

The cooling swing setting 

is adjustable from 0.2˚ to 

2˚. For example: A swing 

setting of 0.5˚ will turn the 

cooling on at approximately 

0.5˚ above the setpoint 

and turn the cooling off at 

approximately 0.5˚ below 

the setpoint.

The swing setting often called 

“cycle rate”, “differential”, or 

“anticipation” is adjustable. A 

smaller swing setting will cause 

more frequent cycles and a larger 

swing setting will cause fewer 

cycles.

Heating 

Swing

CO

dF

0.5˚

The heating swing setting is 

adjustable from 0.2˚ to 2˚. 

For example: A swing setting 

of 0.5˚ will turn the heating 

on at approximately 0.5˚ 

below the setpoint and turn 

the heating off at 0.5˚ above 

the setpoint.

0.4˚

HE

dF

Swing Setting Tip

The second stage will turn on at 2x the swing setting.  The second stage 

will turn off when 1x the swing is reached. For example, if the swing 

setting is .5 degrees for heating and the thermostat is set at 70

˚

F, the first 

stage will turn on at approximately 69.5

˚

F.  The second stage will turn on 

at 69

˚

F. The second stage will turn off at 69.5

˚

F and the first will turn off 

at 70.5

˚

F.  If the third stage is used, it will turn on at 68.5

˚

F and turn off at 

approximately 69

˚

F.

0.5

dF

0.5

EMERGENCY

HEAT

Summary of Contents for TP-S-955WH

Page 1: ...ctable wireless communication options Each component has a jumper switch label FSK and ASK Default setting FSK All components must be set to the same position for wireless communication Both modes uti...

Page 2: ...cal Mount Horizontal Mount For horizontal mount put one screw on the left and one screw on the right For vertical mount put one screw on the top and one screw on the bottom To connect the base module...

Page 3: ...base module in locations That are behind a chimney Where temperature could exceed 150 F Where rain or snow or extreme hot or cold is possible Note This base module is NOT weatherproof Wireless Communi...

Page 4: ...erminal block can keep the thermostat from fitting on the subbase correctly or cause system operation issues Installation Tip Max Torque 6in lbs Wiring If you are replacing a thermostat make note of t...

Page 5: ...compressor run time to OFF 3 4 or 5 minutes If 3 4 or 5 is selected the compressor will run for at least the selected time before turning off Minimum Compressor OnTime OFF You can adjust the room temp...

Page 6: ...up Steps Adjustment Options Default LCDWillShow You can configure the thermostat to operate a 3 stage heat pump system 2H 2C 2 heat 2 cool 3H 2C 3 heat 2 cool This feature is shown only if the HEAT PU...

Page 7: ...OR FINDING SENSOR Disable the sensor on the master At least one indoor remote sensor must be connected to disable the local sensor LocalTemp Sensor YES enables local sensor NO disables local sensor YE...

Page 8: ...d Humidity Key Target humidity setpoint keys Note The target humidity setpoint is not programmable Unlike temperature humidity does not change quickly and should not be programmed Note Humidity is onl...

Page 9: ...are now programming the OCCUPIED time period for that day 4 Use the or key to make your time selection for the OCCUPIED time period Note If you want the fan to run continu ously during this time peri...

Page 10: ...customize your 7 day Program schedule follow these steps Monday Repeat steps 4 through 6 for the remaining days of the week A Note About Auto Changeover In Auto you have the ability to switch between...

Reviews: