background image

Technician Setup

This feature allows you to set a 

minimum cooling setpoint limit. 

The setpoint temperature cannot 

be lowered below this value.

This feature allows you to set a 

maximum heating setpoint limit. 

The setpoint temperature cannot 

be raised above this value.

Heating 

Temperature 

Setpoint 

Limit

Use the         or         key to 

select the maximum heat 

setpoint.

This feature allows you to display 

temperatures in either Fahrenheit 

or Celsius.

˚F or ˚C

˚F

˚F for Fahrenheit

˚C for Celsius

You can select either a 12 or 24 

hour clock setting.

12 or 24

Hour Clock 

90

74

12H

12

HOUR CLOCK

Cooling 

Temperature 

Setpoint 

Limit

Use the         or         key to 

select the minimum cool 

setpoint.

44

44˚F

90˚F

HE

CO

O

F

Use the         or         key to 

select 12 or 24 hour clock.

This feature will start heating 

early to bring the building 

temperature to its programmed 

setpoint by the beginning of the 

WAKE, OCCUPIED time period. 

Morning 

Recovery

ON

Use the         or         key to 

turn on or off.

You can configure this thermostat 

to have a 7 day program, a 

5+1+1 program or as

nonprogrammable.

Program 

Options

5d

Use the         or         key to 

select 

7d

 for 7 day, 

5d

 for 

5+1+1, or 

0d

 for 

nonprogrammable.

5d

The display light can be 

configured to stay on all the 

time or come on when any key 

is pressed.

NOTE: HARDWIRE ONLY

Keeping the display light 

continually “ON” will greatly 

reduce battery life.

The pre-occupancy fan settings 

will energize the fan before 

the occupied time to provide 

ventilation prior to scheduled 

occupancy.

This feature only shows if the

technician setup step for time 

periods is set to 2C or 4C.

Pre-Occupancy 

Fan

You can select the 

pre-occupancy fan from OFF, 

1, 2, or 3 hours.

If 1, 2, or 3 is selected, the 

fan will turn on that many 

hours prior to the scheduled 

occupied time period.

Tech Setup Steps

Allows you to put your phone 

number in the display.

You can choose ON or OFF.

Contractor 

Call Number

If selected ON, you will 

see the input screen after 

pressing

 NEXT STEP

.

Use the          or         key to 

select the desired number 

and the 

        

or 

        

key to 

move from one character to 

another. See note below for 

operation.

Adjustment Options

Default

LCD Will Show

When any key is pressed an 

audible beep will sound.

You can choose ON or OFF.

Beep 

PRE 
OCCUPY 
FAN

Display Light

Use the         or         key to to 

turn on or off.

OFF configures the display 

light to come on when the 

light key or any button is 

pressed.

ON configures the display 

light to stay on.

Time Periods

You can configure this thermostat

to have 2 or 4 programmable time 

periods per day. 4 time periods 

are Wake, Leave, Return & Sleep. 

2C time periods are Occupied 

& Unoccupied. 4C time periods 

are Occupied 1, Unoccupied 1, 

Occupied 2, & Unoccupied 2.

Use the          or          key to 

select 

4, 2c

, or 

4c

 time periods 

per day.

4

OFF

OFF

dL

If ON is selected the beep 

will sound.

If OFF is selected there is no 

sound.

4

OFF

OFF

ON

b

Tech Setup Steps

Adjustment Options

Default

LCD Will Show

Contractor Call Number Note

If contractor call number is selected ON, the phone number entered will 

show in the display if there has been a continuous call for heating or 

cooling for 24 hours or if the light button is held down for 3 seconds.  To 

remove the phone number from the display, hold the light button down 

for 3 seconds. 

Technician Setup

OFF

Technician Setup

Technician Setup

Tech Setup Steps

Adjustment Options

Default

LCD Will Show

You can configure the thermostat 

to operate a 3 stage heat pump 

system.

2H 2C = 2 heat, 2 cool

3H 2C = 3 heat, 2 cool

This feature is shown only if the 

HEAT PUMP technician setup 

step is ON.

Stages of 

Heat

Use the         or          key to 

change between 2 or 3 

stages of heat. 2 heat will 

use Y1 as first stage and W2 

as auxiliary.

3 heat will use Y1 as the first 

stage, Y2 as the second stage 

and W2 as the auxiliary.

2H2C

2

STAGES

STAGE

Balance Point 

Temp

Only shows if Heat 

Pump is turned 

ON and Remote 

Sensor is set to 2.

Requires 

Outdoor Sensor

An outdoor temperature 

ABOVE

 this setting will LOCKOUT 

the auxilary heat terminal (W2), 

and ONLY ALLOW the heat pump/

compressor terminals (Y’s) to 

energize.

An outdoor temperature 

BELOW

 this setting can perform 

2 different ways, depending on 

the previous 

Gas Aux/Dual 

Fuel setting.

1. If Gas Aux/Dual Fuel is set 

OFF

 

(Default-typical Electric Aux 

setting) This will allow both heat 

pump (Y’s) and auxiliary heat 

(W2) to run together.

2. If Gas Aux/Dual Fuel is set 

ON

 

(typical Gas Auxilary/Dual Fuel 

setting) This will LOCKOUT the 

heat pump (Y’s) and ONLY ALLOW 

the auxiliary heat (W2) to

 energize

NO

Use the          or          to select  

YES or NO. 

If set to YES then use       or  

to select Balance point 

Temperature of 10, 20, 30, 

35, 40, 45 or 50 degrees.

Balance point run time will allow 

the W2 auxiliary terminal to 

energize even if outdoor 

temperature is above the selected 

balance point temperature. 

If enabled, auxiliary will energize 

for the current cycle after the 

balance point run time has 

expired.

Balance 

Point Run 

Time

YES

15, 30, 45, 60, 75, 90 

continuous run time 

minutes.

BALANCE 
RUNTIME

NO

Requires Outdoor Sensor

The amount of over cooling 

allowed when using A/C to 

remove humidity. This screen is 

only shown when ON is selected 

in the “Dehumidify with AC” tech 

setup step.

Over Cool

Limit

Use the         or          key to 

select YES or NO.

If selected Yes, allows over 

cooling to be used to control 

humidity in cool mode. If NO 

is slected the system will not 

use over cooling.

NO

Dehumidify 

with AC

This feature forces the A/C to run 

longer to remove humidity when 

needed. The A/C will “over cool” 

the room a few degrees until the 

humidity reaches the desired 

setpoint.

Use the         or         key to 

select the maximum number 

of degrees of over cool.

Options are: 2, 3, 4, 5 

Degrees.

3

3

d HUMIDIFY 
AC

This feature allows the installer 

to change the calibration of the 

ambient humidity displayed.

Humidity

Calibration

OFF

Dehumidify

This feature removes humidity 

when SYSTEM key is in cool.

See terminal options on following 

page.

Use the          or          key to 

adjust the calib/-3.

1= approx. 5%

0

0

Tech Setup Steps

Adjustment Options

Default

LCD Will Show

This feature adds humidity when 

SYSTEM key is in heat.

See terminal options on following 

page.

Humidify

Use the          or          key to 

turn on of off.

If ON is selected the humidity 

will be displayed on the main 

screen and HUM terminal 

will energize when humidity 

setpoint is above ambient 

humidity in Heat mode.

OFF

HUMIDITY

DEHUMIDIFY

HUM
CALIBRATE

OFF

OFF

Use the          or         key to 

turn on of off.

If ON is selected the humidity 

will be displayed on the main 

screen and DHM terminal 

will energize when humidity 

setpoint is below ambient 

humidity in Cool mode.

OVER COOL
LIMIT

Options for how the HUM 

terminal energizes.

HUM

Terminal

Use the         or         key to 

select the one of the four 

options.

View the HUM terminal chart 

below for an explanation of 

these options.

1

1

HUM 
TERMINAL

YES 50

BALANCE

POINT

Summary of Contents for TP-S-955WH

Page 1: ...ctable wireless communication options Each component has a jumper switch label FSK and ASK Default setting FSK All components must be set to the same position for wireless communication Both modes uti...

Page 2: ...cal Mount Horizontal Mount For horizontal mount put one screw on the left and one screw on the right For vertical mount put one screw on the top and one screw on the bottom To connect the base module...

Page 3: ...base module in locations That are behind a chimney Where temperature could exceed 150 F Where rain or snow or extreme hot or cold is possible Note This base module is NOT weatherproof Wireless Communi...

Page 4: ...erminal block can keep the thermostat from fitting on the subbase correctly or cause system operation issues Installation Tip Max Torque 6in lbs Wiring If you are replacing a thermostat make note of t...

Page 5: ...compressor run time to OFF 3 4 or 5 minutes If 3 4 or 5 is selected the compressor will run for at least the selected time before turning off Minimum Compressor OnTime OFF You can adjust the room temp...

Page 6: ...up Steps Adjustment Options Default LCDWillShow You can configure the thermostat to operate a 3 stage heat pump system 2H 2C 2 heat 2 cool 3H 2C 3 heat 2 cool This feature is shown only if the HEAT PU...

Page 7: ...OR FINDING SENSOR Disable the sensor on the master At least one indoor remote sensor must be connected to disable the local sensor LocalTemp Sensor YES enables local sensor NO disables local sensor YE...

Page 8: ...d Humidity Key Target humidity setpoint keys Note The target humidity setpoint is not programmable Unlike temperature humidity does not change quickly and should not be programmed Note Humidity is onl...

Page 9: ...are now programming the OCCUPIED time period for that day 4 Use the or key to make your time selection for the OCCUPIED time period Note If you want the fan to run continu ously during this time peri...

Page 10: ...customize your 7 day Program schedule follow these steps Monday Repeat steps 4 through 6 for the remaining days of the week A Note About Auto Changeover In Auto you have the ability to switch between...

Reviews: