3. Setup and Connections
33
j.
Milliseconds TX Delay – This is the minimum amount of time after receiving a
response before the next message can be sent out. Valid value range is from 1 to
65535.
k.
Save settings by clicking the “Save” button.
14.
Port x ID Remap
a.
To access this screen, click the “Next” button or click the “Port x ID Remap” link
on the left side of the screen.
b.
This screen allows you to set Modbus Slave ID Remap settings.
Figure 39. Port ID Remap Screen
c.
The first box in line is the start of the remap range on the serial port you want to
remap. Valid value range is from 1 to 247.
d.
The second box in line is the last serial port of that range. Valid value range is
from 1 to 247.
e.
The third box in line is the starting ID of a range to remap to. Valid value range is
from 1 to 247.
f.
The fourth box in line is auto filled in based on the range filled in the first 3
boxes. Valid value range is from 1 to 247.
g.
Save settings by clicking the “Save” button.
15.
Modbus ID Routing
a.
To access this screen click the “Next” button or click the “Modbus ID Routing”
Link on the left side of the screen.