Recommended max. fuse
Power
[kW]
Bussmann
Type JFHR2
2)
Littel fuse
JFHR2
Ferraz-
Shawmut
JFHR2
4)
Ferraz-
Shawmut
J
0.25–0.37
FWX-5
-
-
HSJ-6
0.55–1.1
FWX-10
-
-
HSJ-10
1.5
FWX-15
-
-
HSJ-15
2.2
FWX-20
-
-
HSJ-20
3.0
FWX-25
-
-
HSJ-25
3.7
FWX-30
-
-
HSJ-30
5.5
FWX-50
-
-
HSJ-50
7.5
FWX-60
-
-
HSJ-60
11
FWX-80
-
-
HSJ-80
15–18.5
FWX-125
-
-
HSJ-125
22
FWX-150
L25S-150
A25X-150
HSJ-150
30
FWX-200
L25S-200
A25X-200
HSJ-200
37
FWX-250
L25S-250
A25X-250
HSJ-250
Table 10.20 200–240 V, Frame Sizes A, B and C
1) KTS fuses from Bussmann may substitute for KTN for 240 V adjustable frequency drives.
2) FWH fuses from Bussmann may substitute for FWX for 240 V adjustable frequency drives.
3) A6KR fuses from FERRAZ SHAWMUT may substitute for A2KR for 240 V adjustable frequency drives.
4) A50X fuses from FERRAZ SHAWMUT may substitute for A25X for 240 V adjustable frequency drives.
Recommended max. fuse
Power
[kW]
Bussmann
Type RK1
Bussmann
Type J
Bussmann
Type T
Bussmann
Type CC
Bussmann
Type CC
Bussmann
Type CC
0.37–1.1
KTS-R-6
JKS-6
JJS-6
FNQ-R-6
KTK-R-6
LP-CC-6
1.5–2.2
KTS-R-10
JKS-10
JJS-10
FNQ-R-10
KTK-R-10
LP-CC-10
3
KTS-R-15
JKS-15
JJS-15
FNQ-R-15
KTK-R-15
LP-CC-15
4
KTS-R-20
JKS-20
JJS-20
FNQ-R-20
KTK-R-20
LP-CC-20
5.5
KTS-R-25
JKS-25
JJS-25
FNQ-R-25
KTK-R-25
LP-CC-25
7.5
KTS-R-30
JKS-30
JJS-30
FNQ-R-30
KTK-R-30
LP-CC-30
11
KTS-R-40
JKS-40
JJS-40
-
-
-
15
KTS-R-50
JKS-50
JJS-50
-
-
-
18
KTS-R-60
JKS-60
JJS-60
-
-
-
22
KTS-R-80
JKS-80
JJS-80
-
-
-
30
KTS-R-100
JKS-100
JJS-100
-
-
-
37
KTS-R-125
JKS-125
JJS-125
-
-
-
45
KTS-R-150
JKS-150
JJS-150
-
-
-
55
KTS-R-200
JKS-200
JJS-200
-
-
-
75
KTS-R-250
JKS-250
JJS-250
-
-
-
Table 10.21 380–500 V, Frame Sizes A, B and C