background image

The 

DREC-C

 allows one mode of

 

automatic reclosing:

-

Reclosing

 

by insulation

, the device does not reclose until the leakage has disap-

peared.

4�4�2�1�- Reclosing by insulation

Following a time delay after a disconnection due to an RCCB trip, the 

DREC-C

 makes a meas

-

urement to check whether there is a leakage current. If there is none it begins to reclose.

The 

DREC-C

 attempts a maximum of 3 measurements to check the leakage current; following 

this the unit stays locked and does not automatically reclose.

If the time between a reclosure and the next trip is greater than the restart time, the reclosing 

attempts start over at zero.

The delay and restart times depend on the number of attempts the reclosing device has made, 

as shown in 

Table 5

.

Table 5: Delay and Restart Times�

Reclosures

1

2

3

Delay

Restart

Delay

Restart

Delay

 Restart 

<3 sec.

10 sec.

20 sec.

20 sec.

180 sec.

60 sec.

The leakage current will be supervised by measuring the resistance downstream of the tripped 

RCCB.

4�4�2�2�- Restarting the reclosing system meter

There are two ways to restart the internal reclosing system meter:

-

Manually

, by moving the mode selector switch from ON to OFF position  and back to

ON.

-

Automatically

, when the restart time elapses after the last reclosing without tripping

again.

4�4�2�3�- Restart in case of blocking

In case of blocking of the device, the start-up sequence is:

1�-  

Check installation.

2�- 

 Put the mode selector switch in Manual Mode (OFF).

 3�-

  Lift the RCCB cover.

 4�- 

 Put the RCCB contact in ON mode.

 5�-

  Lower the RCCB cover.

 6�-

  Put the mode selector switch in Manual mode (ON).

Note:

 

The switch has an M2 hole where you can attach a seal or a padlock to block access to 

the RCCB and any other attempts at manual reclosing (

Figure 7

).

14

DREC-C 

Instruction Manual

Summary of Contents for DREC Compact

Page 1: ...INSTRUCTION MANUAL M202BVM 03 21A RCCB with automatic reclosing device DREC Compact DREC C...

Page 2: ...2 DREC C Instruction Manual...

Page 3: ...ng should be taken into consideration Incorrect handling or installation of the unit may result in injury to personnel as well as damage to the unit In particular handling with voltages applied may re...

Page 4: ...LATION 7 3 3 CONNECTION 8 3 3 1 CONNECTION DIAGRAM 2 POLE MODEL DREC C 2P 8 3 3 2 CONNECTION DIAGRAM 4 POLE MODEL DREC C 4P 9 4 OPERATION 10 4 1 DESCRIPTION 10 4 2 LEDs 11 4 3 START UP 12 4 3 1 AUTOMA...

Page 5: ...d may differ from the original device SYMBOLS Table 2 Symbols Symbol Description In compliance with the relevant European directive Device covered by European directive 2012 19 EC At the end of its us...

Page 6: ...mode is used for high sensitivity protection so that the device only recloses when the fault that caused tripping has disappeared The rest of the models imple ment the timed reclosing mode to ensure p...

Page 7: ...lting from the use of non original products or accessories or those made by other manufacturers If you detect any operational faults in the device or in its protection system remove the device from se...

Page 8: ...anent failure AUTO and REC LEDs are lit you must check the RCCB and the installation If the installation of the device is done with the RCCB in the OFF state when panel receives voltage the device wil...

Page 9: ...ON DIAGRAM 4 POLE MODEL DREC C 4P CARGA LOAD L3 N L1 L2 Figure 2 Connection diagram DREC C 4P Three phase system CARGA LOAD F N Figure 3 Connection diagram DREC C 4P Single phase system 9 Instruction...

Page 10: ...t important pieces of device LEDs Protection cover TEST key Mode selection switch RCCB Control module Figure 4 Description of the DREC C 2P LEDs Protection cover TEST key Mode selection switch RCCB Co...

Page 11: ...e has been initiated ON Slow flashing Automatic OFF Rearm sequence initiated Time delay of the rearm sequence if applica ble ON Fast flashing Automatic OFF Rearm sequence initiated Monitoring the leak...

Page 12: ...the RCCB cover 5 Put the mode selector switch in Automatic Mode ON Note The switch has an M2 hole where you can attach a seal or a padlock to block access to the RCCB and any other attempts at manual...

Page 13: ...isable the unit s automatic reclosing device Figure 8 The RCCB must be reclosed manually The AUTO and REC LEDs are off Figure 8 DREC C in manual mode with mode selector switch at OFF 4 4 2 AUTOMATIC T...

Page 14: ...s Reclosures 1 2 3 Delay Restart Delay Restart Delay Restart 3 sec 10 sec 20 sec 20 sec 180 sec 60 sec The leakage current will be supervised by measuring the resistance downstream of the tripped RCCB...

Page 15: ...requently Test sequence Figure 10 1 Press the TEST T key 2 Check that the RCCB jumps to OFF position TEST OFF Figure 10 RCCB Test Sequence In the event of a Test sequence failure contact the after sal...

Page 16: ...2P 40 300 300 mA DREC C 2P 63 300 DREC C 4P 40 30 30 mA DREC C 4P 63 30 DREC C 4P 40 300 300 mA DREC C 4P 63 300 Resistance to surges class A AC 250A 8 20 s class S 3000A 8 20 s Resistance to short ci...

Page 17: ...c Colour RAL 7035 Dimensions mm Figure 11 and Figure 12 Standard Residual current operated circuit breakers without integral overcurrent pro tection for household and similar uses RCCB s Part 1 Genera...

Page 18: ...81 91 5 35 5 101 55 87 5 45 76 Figure 12 DREC C 4P dimensions 18 DREC C Instruction Manual...

Page 19: ...al code or that surpasses the limits indicated in the techni cal and environmental features of this manual VMC accepts no liability due to the possible damage to the unit or other parts of the install...

Page 20: ...VMC C Montcada 7 Pol Ind Les Pereres 08130 Santa Perp tua de Mogoda Barcelona Tel 34 935 748 206 Fax 34 935 748 248 www vmc es info vmc es...

Reviews: