4.3.- START-UP
Once the device is installed you must carry out the following start-up sequence for it to work
properly.
4�3�1�- AUTOMATIC MODE
If the device is going to operate in automatic mode, see Section
,
the start-
up sequence is:
1�-
Put the mode selector switch in Manual Mode (OFF).
2�-
Lift the RCCB cover.
3�-
Put the RCCB contact in ON mode.
4�-
Lower the RCCB cover.
5�-
Put the mode selector switch in Automatic Mode (ON).
Note
:
The switch has an M2 hole where you can attach a seal or a padlock to block access to
the RCCB and any other attempts at manual reclosing (
).
Figure 7: Switch’s M2 hole to seal access to the RCCB�
4�3�2�- MANUAL MODE
If the device is going to operate in manual mode, see Section
,
the start-up
sequence is:
1�-
Put the mode selector switch in Manual Mode (OFF).
2�-
Lift the RCCB cover.
3�-
Put the RCCB contact in OFF mode.
4�-
Lower the RCCB cover (optional).
12
DREC-C
Instruction Manual