background image

VGZ-005 / 20120202.0

 

BX42E-SN /

 

Page 11

CHIMNEY CONNECTIONS continued …

Figure 14 - Fireplace Conversion

enough insulation and/or air cooling on the base, back 
and sides so they can be safely installed in direct con-
tact with combustible floors and walls. Although many 
prefabricated fireplaces carry endorsements from na-
tionally recognized organizations for use as fireplaces, 
they have not been tested for connection to wood stove 
heaters. Connecting a stove to such a device will void 
the manufacturer’s warranty.

Steel-lined fireplaces are constructed with  

1/4” firebox liner, an air chamber in connection with 8” 
of masonry. These can be safely used with wood burn-
ing stoves. They contain all the essential components 
of a fireplace, firebox, damper, throat, smoke shelf, 
and smoke chamber. Many look identical to masonry 
fireplaces and should be checked carefully before con-
necting a stove to them.

Venting a stove directly into a fireplace does not 

meet code and should not be attempted. The stove war-
ranty will be void with such an installation. Do not create 
a hazard in your home by connecting in this manner.

FIREPLACE INSTALLATION

Directly connecting the stovepipe into the existing 

masonry chimney (figure 14 “Type A” Fireplace Conver-
sion) of the fireplace is the only approved method of 
installation. This is a complicated and involved process 
and to insure safety should only by done by a qualified 
installer.
1.  An entry hole must be cut through the masonry and 

tile liner with minimal damage to the liner. At least 8” 
of liner must remain below the entry position. When 
locating the stove and stovepipe, all minimum clear-
ances must be observed from combustible surfaces 
including mantels, combustible trimwork, ceilings 
and walls. Positioning the center of the stove pipe 
entry into the chimney 24” below the ceiling should 
insure proper clearance for a 6” stovepipe.

2.  Install a metal or fire clay (5/8” minimum thickness) 

thimble. Make sure the thimble is flush with the inner 
surface of the chimney liner and does not protrude 
into the flue (see figures 10).

3.  Secure the thimble with refractory mortar. The 

thimble should be surrounded by 12” of solid unit  
masonry brickwork or 24” of stone.

4.  Install the stovepipe into the thimble as far as pos-

sible without extending past the flue lining (see 
figures 9 & 10).

5.  A small airspace (about 1/2”) should remain 

between the stovepipe and thimble to allow for 
expansion of the pipe. Seal this airspace with high-
temperature caulking or ceramic wool.

6.  Secure and seal the damper in the closed posi-

tion using high-temp caulking, ceramic wool, or 
furnace cement. Also check to see if the chimney 
has a cleanout. If it does, make sure it is closed and 
sealed as well. A leaky cleanout will greatly reduce 
draft efficiency.

If you have any questions regarding venting your 

stove, contact the manufacturer or contact the Na-
tional Fire Protection Association (NFPA) and request 
a copy of the latest editions of NFPA Standard 211 
and NFPA Standard 908. Their address is:

 Battery March Park, Quincy, MA 02269.

Call us at 1-866-667-8454 

NorthlineExpress.com

www.NorthlineExpress.com

Summary of Contents for BX42E

Page 1: ...save this manual for future reference NOTE THIS STOVE IS NOT A UL LISTED STOVE READ ALL INSTRUCTIONS CAREFULLY BEFORE INSTALLING OR OPERATING THIS STOVE FAILURE TO FOLLOW INSTRUC TIONS MAY RESULT IN PROPERTY DAMAGE BODILY INJURY OR EVEN DEATH REFER TO MARKINGS ON STOVE LABELS FOR ADDITIONAL INFORMATION NOTE IT IS RECOMMENDED INSTALLATION BE COMPLETED BY A QUALIFIED HEATING EQUIPMENT INSTALLER DO N...

Page 2: ...03 HT Residential Type and Building Heating Appliance Chimney Use a 6 152mm diameter chimney that is high enough to give a good draft See specifics in Chimney Connections instructions 10 Be sure that your chimney is safely constructed and in good repair Have the chimney inspected by the fire department or a qualified inspector Your insurance company should be able to recommend a qualified inspecto...

Page 3: ...S 30 A WOOD BURNING STOVE MUST NEVER BE INSTALLED IN A HALLWAY OR NEAR A STAIR CASE as it may block egress in the event of a fire 31 DO NOT INSTALL IN A SLEEPING ROOM SAFETY INSTRUCTIONS continued DO NOT INSTALLTHIS UNIT IN AN ALCOVE OR INSIDE A FIREPLACE 32 Install at least one smoke detector on each floor of your home Detectors should be located away from the heating appliance to avoid false ala...

Page 4: ...ting Precautions Warnings 12 Wood Types Sizes 12 Starting a Fire 12 Adding Fuel 13 Service Hints Creosote Formation Prevention Need for Removal 13 Stove Joints 14 Gasket Replacement 14 Parts Deluxe Boxwood 15 Floor Protector Calculations 16 Chimney Connection Systems Clearances 17 NOTE A PROFESSIONAL LICENSED HEAT ING AND COOLING CONTRACTOR MUST BE CONSULTED IF YOU HAVE QUESTIONS REGARDING THE INS...

Page 5: ...Chimney Connection 6 black steel 24 ga min straight or elbow as required 1 2 Sheet Metal Screws Chimney Existing 6 Lined Ma sonry Chimney or 6 Inside Dia listed Type HT chimney Furnace Cement manufacturer recommends Rutland Code 78 or equivalent NOTICE Vogelzang International Corp grants no warranty stated or implied for the installation or maintenance of your wood stove and assumes no responsibil...

Page 6: ...nd at least 18 beyond the front of the hearth to the sides and beyond the rear of the stove The area under a horizontal run of the chimney connector must also be protected extending two 2 inched beyond the outer dimension of the horizontal connector The minimum sized floor protector for this stove is 52 x 74 Consult local building codes and fire protection ordnances CAUTION FIRE HAZARD CARPETING A...

Page 7: ...L CONTAINING COMBUSTI BLEMATERIALSUCHASWOODENSTUDSOR DRYWALLANDFACEDWITHBRICKORSTONE MUST BE CONSIDERED A COMBUSTIBLE SURFACE 6 DO NOT INSTALL THIS STOVE IN A MOBILE HOME MANUFACTURED HOME TRAILER OR TENT NO EXCEPTIONS HUD Federal Stan dard 24 CFR Ch XX Figure 7 Minimum Clearance Dimensions from Combustible Surfaces 7 The clearances provided are minimum dimensions determined by the NFPA Installati...

Page 8: ... allow any condensation in the flue to run back into the firebox 2 Horizontal pipe runs must slope upwards towards the chimney at least 1 4 6 4mm per foot of horizontal run 3 You must have at least 18 457mm of clearance between any horizontal piping and the ceiling 4 The pipe cannot extend into the chimney flue figure 9 5 Secure pipe elbow sections with three sheet metal screws at each joint to ma...

Page 9: ...e held responsible for external factors leading to less than optimal drafting Should you have a problem with inadequate draft you should contact a licensed heating and cooling con tractor for assistance in solving the problem IMPORTANT Installation Points 1 Size chimney flue to stove collar This stove requires a minimum of a 6 152mm diameter flue 2 Never connect this unit to a chimney serving an o...

Page 10: ...CE In some instances people desire to convert an ex isting fireplace for stove use Usually safe connection to an existing masonry chimney requires more work than using a prefabricated chimney The existing fireplace must be closed and sealed at the damper with high temperature caulk ceramic wool or furnace cement Prior to installation clean and inspect the existing flue and smoke shelf Installation...

Page 11: ...he masonry and tile liner with minimal damage to the liner At least 8 of liner must remain below the entry position When locating the stove and stovepipe all minimum clear ances must be observed from combustible surfaces including mantels combustible trimwork ceilings and walls Positioning the center of the stove pipe entry into the chimney 24 below the ceiling should insure proper clearance for a...

Page 12: ...oor and secure tightly 6 Adjust the collar draft damper and door spin draft control The more closed the spin draft is set the lower and slower the fire will burn The more open the faster and hotter the fire will burn Do not over fire the stove continued on next page CAUTION HOUSE FIRE HAZARDS DO NOT STORE WOOD ON FLOOR PROTEC TOR UNDERNEATH STOVEPIPE OR ANY WHEREWITHIN MINIMUM CLEARANCES FROM COMB...

Page 13: ...ER AND SPIN DRAFTTO RE DUCETHE AIR SUPPLY AND SLOW DOWNTHE FIRE TOO MUCH WOOD OR BURNING NON RECOMMENDED MATERIALS SUCH AS TRASH OR FLAMMABLE LIQUIDS MAY CAUSE OVER FIRING continued on next page CAUTION DO NOT OVER FIRE APPLIANCE CAUTION SLOW BURNING FIRES AND EX TENDED USE MAY CAUSE EXCESSIVE CREO SOTE BUILDUP IGNITION OF CREOSOTE BUILDUP OR OVERFIRING MAY CAUSE A CHIMNEY FIRE CHIMNEY FIRES BURN ...

Page 14: ...buildup of condensation or creosote in the chimney are warnings that the chimney is NOT functioning properly Correct the problem before using the stove Following are some possible causes for improper draft 1 The connector stovepipe may be pushed into the chimney too far stopping the draft 2 If the chimney temperature is too cool water will condense in the chimney and run back into the stove Creoso...

Page 15: ... parts Part No Description Qty 42 01 Leg 4 42 02 Bottom 1 42 03 Side 2 42 04 Back 1 42 05 Front 1 42 06 Door 1 42 07 Top 1 42 08 Damper Slide Draft 1 42 09 Lid 2 42 10 Lid Support 1 42 11 Hearth 1 42 12 Damper Collar Assembly 1 42 13 Handle Assembly 1 42 14 Lid Lifter L 1 1 42 15 42 16 S Hook used to hang lid lifter 1 42 17 Spin Draft 1 42 18 Door Latch 1 42 19 Gasket Door 1 4 dia fiberglass 1 HP ...

Page 16: ...late R value of proposed material s b For multiple layers add R values of each layer to determine overall R value 3 If the overall R value of the floor protector system is equal to or greater than the floor protector specifications given the alternate is acceptable Definitions Thermal conductance C BTU W hr ft2 F m2 K Thermal conductivity k Btu inch W Btu hr ft2 F m K hr ft F Thermal resistance R ...

Page 17: ...52mm of glass fiber insulation Opening shall be covered and thimble supported with a sheet steel support minimum 24 gauge in thickness D Chimney Section Pass through Solid insulated listed factory built chimney length with an inside diameter 2 51mm larger than the chimney connector and having 1 25 4mm or more of insulation serving as a pass through for a single wall sheet steel chimney connector o...

Page 18: ...d health Respectfully yours Proprietor COMPANY TESTIMONY Vogelzang International Corporation 400 West 17th Street Holland Michigan 49423 www vogelzang com Phone 1 616 396 1911 Fax 1 616 396 1971 FOR GOD SO LOVED THE WORLD THAT HE GAVE HIS ONLY BEGOTTEN SON THAT WHOEVER BELIEVES IN HIM SHALL NOT PERISH BUT HAVE ETERNAL LIFE JOHN 3 16 MADE IN CHINA SteveVogelzang DO NOT USE THIS STOVE IN A MOBILE HO...

Reviews: