background image

VGZ-026 / 20120306.0

  

Vogelzang International Corp. 

TR001 DEFENDER™

 / 

Page 9

Fig. 8 - Chimney Construction Through Roof

Fig. 9 - Chimney Connection to Firebox  

Through Masonry Wall

CHIMNEY CONNECTIONS continued …

MANUFACTURED CHIMNEY

Refer to chimney and chimney connector maker’s 

instructions for installation and use.

Use only 6” diameter listed chimney UL 103 HT 

(U.S.) or ULC-S629 (Canada). Chimney made to this 
listing is High Temperature rated to 2100 degrees 
Fahrenheit. Use chimney from only one manufacturer.

 

NEVER MIX BRANDS. Carefully follow the chimney 
manufacturer’s stated requirements and clearances. 
Use the chimney manufacturer’s attic guards, roof sup-
ports, flashing and fire stops when passing through a 
ceiling. Use a listed thimble when passing through a 
combustible wall. Do not use makeshift compromises 
during installation. 

WARNING: DO NOT USE A SINGLE-WALL CON-
NECTION PIPE AS A CHIMNEY!

When using a pre-existing chimney, have it’s condi-

tion and installation inspected before using. Make sure 
that the chimney meets all of the UL rating requirements 
listed above. Be aware that not all manufactured chim-
ney is of the UL 103 HT or ULC-S629 type.

NOTE: It is recommended that you contact a li-

censed heating and cooling contractor (consult your 
local yellow pages) for chimney installation.

Manufactured chimney with the proper required UL 

listing is available from most home centers, hardware 
stores, and HVAC supply stores.

If you have access to the internet, you may wish 

to view chimney manufacturers’ information on-line. 
See, www.duravent.com, www.selkirkinc.com, or www.
mtlfab.com.

VENTING TO EXISTING FIREPLACE

In some instances, people desire to convert an ex-

isting fireplace for stove use. Usually, safe connection to 
an existing masonry chimney requires more work than 
using a prefabricated chimney. The existing fireplace 
must be closed and sealed at the damper with high-
temperature caulk, ceramic wool, or furnace cement. 
Prior to installation, clean and inspect the existing flue 
and smoke shelf. Installation should be designed so 
the system can be dismantled for periodic cleaning and 
inspection. Before conversion, make sure the existing 
chimney is structurally sound, the chimney incorporates 
a flue liner and make sure it is in good condition. (A flue 
liner consists of clay tile that protects the brickwork of 
a chimney. If a chimney does not have a liner, or it is 
damaged, have it relined by a professional. Do Not use 
a chimney that is unlined or damaged!) If you have 
any question regarding the condition of the chimney, 
consult a qualified licensed contractor, qualified en-
gineer, competent mason, certified Chimney Sweep, 

Continued on next page 

Summary of Contents for DEFENDER TR001

Page 1: ...PROPERLY INSTALLED A HOUSE BUILDING FIRE MAY RESULT FOR YOUR SAFETY CONTACT LOCAL BUILDING OR FIRE OFFICIALS ABOUT PERMITS RESTRICTIONS AND INSTALLATION REQUIREMENTS FOR YOUR AREA Vogelzang International Corporation 400 West 17th Street Holland Michigan 49423 www vogelzang com Phone 1 616 396 1911 Fax 1 616 396 1971 DEFENDER HIGH EFFICIENCY AIR TIGHT WOODSTOVE EPA Certified 4 21grams hr Model TR00...

Page 2: ...R APPLIANCE 9 DO NOT CONNECT A WOOD BURNING STOVE TO AN ALUMINUM TYPE B GAS VENT This is not safe Use approved masonry or an Underwrit ers Laboratories Listed UL 103 HT US ULC S629 CDN Residential Type and Building Heating Ap pliance Chimney Use a 6 152mm diameter chim ney that is high enough to give a good draft See specifics in Chimney Connections instructions 10 Be sure that your chimney is saf...

Page 3: ... height or in such a manner that it creates a hazard when opening the door 28 NEVER LEAVE THE STOVE UNATTENDED with door open Always close the door after ignition 29 DO NOT CONNECT TO OR USE IN CONJUNC SAFETY INSTRUCTIONS continued TIONWITH ANY AIR DISTRIBUTION DUCTWORK UNLESS SPECIFICALLY APPROVED FOR SUCH INSTALLATIONS 30 A WOOD BURNING STOVE MUST NEVER BE INSTALLED IN A HALLWAY OR NEAR A STAIR ...

Page 4: ... to obstruct air flow Use four screws provided to fasten the blower to rear heat shield 2 Route the power cord away from stove Do not al low the power cord to touch any hot surfaces Keep power cord at least 12 from stove surfaces 3 Once stove is positioned plug power cord into a grounded 120v outlet 1 The stove must be placed on solid concrete solid masonry or when installed on a combustible floor...

Page 5: ... the stove connector stove pipe and corner clearanc es using the illustrations in figures 1 3 and your local building codes or fire protection ordinances NOTE Drywall faced with brick or stone must be considered a combustible surface 6 Do Not install this stove in a mobile home Manufactured Home trailer or Tent NO EXCEPTIONS HUD Federal Standard 24 CFR Ch xx 7 The clearances provided are minimum d...

Page 6: ...ove and radiates heat more evenly Check to see that all firebricks are in their correct positions and have not become misaligned during shipping or assembly If removed for ease of locating stove firebrick must be replaced before firing See diagrams fig 4a 4c for proper positioning CAUTION NEVER OPERATE STOVE WITH MISSING OR CRACKED FIRE BRICKS Fig 4a Step 1 Bottom Firebrick Installation A A C B A ...

Page 7: ...These provide a better seal 7 The connector pipe must not pass through an at tic or roof space closet or any concealed space or floor ceiling wall or combustible construction See Chimney Connector Systems Clearances page 11 A UL 103 HT Listed U S or ULC S629 CANADA chimney must be used from the first penetration of ceiling or wall to the chimney cap Never use single wall connector pipe as a chimne...

Page 8: ...nufacturer cannot be held responsible for external factors leading to less than optimal drafting Should you have a problem with inadequate draft you should contact a licensed heating and cooling con tractor for assistance in solving the problem IMPORTANT Installation Points 1 Size chimney flue to stove collar This stove requires a 6 diameter flue 2 Never connect this unit to a chimney serving an o...

Page 9: ...tractor consult your local yellow pages for chimney installation Manufactured chimney with the proper required UL listing is available from most home centers hardware stores and HVAC supply stores If you have access to the internet you may wish to view chimney manufacturers information on line See www duravent com www selkirkinc com or www mtlfab com VENTING TO EXISTING FIREPLACE In some instances...

Page 10: ...try hole must be cut through the masonry and tile liner with minimal damage to the liner At least 8 of liner must remain below the entry position When 3 Secure the thimble with refractory mortar The thimble should be surrounded by 12 of solid unit masonry brickwork or 24 of stone 4 Install the stovepipe into the thimble as far as pos sible without extending past the flue lining see figures 4 6 on ...

Page 11: ...ch of glass fiber insulation Opening shall be covered and thimble supported with a sheet steel support minimum 24 gauge in thickness D Chimney Section Pass through Solid insulated listed factory built chimney length with an inside diameter 2 inch larger than the chimney con nector and having 1 inch or more of insulation serving as a pass through for a single wall sheet steel chimney connector of m...

Page 12: ... open slightly DO NOT LEAVE STOVE UNATTENDED WITH DOOR OPEN 5 Add large pieces of wood as the fire progresses being careful not to overload Do not fill firebox beyond firebrick area An ideal coal bed of 1 2 should be established t achieve optimum perfor mance 6 This unit is designed to function most effectively when air is allowed to circulate to all areas of the firebox An idea rake a slight 1 to...

Page 13: ... resume and wood is sufficiently ignited The basic rule of thumb is closed low half way open medium and fully open high ADDING FUEL Add small amounts of fuel each hour or so instead of piling large quantities of fuel at one time This will insure a more complete combustion process and less buildup of tars soot or creosote will occur in the chimney 1 When refueling adjust air inlet control to the fu...

Page 14: ...se impact the glass When closing doors make sure that logs or other objects do not protrude to impact the glass 3 Do not build fires against or that might fall against the glass 4 Do not clean the glass with materials that may scratch or otherwise damage the glass Scratches on the glass can develop into cracks or breaks dur ing operation 5 Never attempt to clean the glass while the unit is hot all...

Page 15: ...himney connector should glow red reduce the fire by clos ing the inlet air control and immediately call the fire department CAUTION A CHIMNEY FIRE MAY CAUSE IGNI TION OF WALL STUDS OR RAFTERS WHICH WERE ASSUMED TO BE A SAFE DISTANCE FROM THE CHIMNEY IF A CHIMNEY FIRE HAS OCCURRED HAVE YOUR CHIMNEY IN SPECTED BY A QUALIFIED EXPERT BEFORE USING AGAIN A fire in the firebox may be smothered by pouring...

Page 16: ...me 1 18 Door Glass 1 19 Gasket 3 8 Fiberglass Glass 1 20 Retainer Glass 1 21 Screws Glass Retainer 8 22 Gasket 3 8 Fiberglass Door 1 23 Hinge Pin 2 24 Nuts for legs 4 25 C Cast Fiber Board 9 x9 x5 8 2 1 Legs 4 2 Heat Sheild 1 3 Handle Slide Draft Spring 1 4 Nickle Trim Top Plate 1 5 Nickle Trim Hearth 1 6 Air Tube Rear 1 7 Air Tube Middle 1 8 Air Tube Front 1 9 Retainer Pins Air Tube 3 10 Z Bar Ba...

Page 17: ...A B A A B A C C A A A C B A A B A A B A A B Firebrick Sides Four 4 A Size Two 2 B Size Firebrick Back Two 2 A Size Two 2 C Size Fire Brick Dimensions A Size 9 x41 2 x11 4 B Size 9 x23 4 x11 4 C Size 9 x31 4 x11 4 A A C B A A B Firebrick Bottom Four 4 A Size Two 2 B Size One 1 C Size FIREBRICK TR001 DEFENDER Part No Description Qty 15 Door Assembly complete 1 16 Handle Assembly complete 1 17 Door F...

Page 18: ...NDER BLOWER OPTION NOTICE ANY REPLACE MENT WIRING MUST HAVE EQUIVALENT INSULA TION AND TEMPERATURE RATING 105 C CAUTION MOVING PARTS CAN CAUSE INJURY DO NOT OPERATEWITH COVER REMOVED DANGER SHOCKHAZARD DISCONNECT POWERSOURCEBEFOREINSTALLATION AND WHENEVER SERVICING BLOWER ASSEMBLY ...

Page 19: ...or protector a Use formulas in step 1 above to calculate R value of proposed material s b For multiple layers add R values of each layer to determine overall R value 3 If the overall R value of the floor protector system is equal to or greater than the floor protector specifications given the alternate is acceptable Definitions Thermal conductance C BTU W hr ft2 F m2 K Thermal conductivity k Btu i...

Page 20: ...ES IN HIM SHALL NOT PERISH BUT HAVE ETERNAL LIFE JOHN 3 16 MADE IN CHINA This Vogelzang heating appliance is safe when installed properly and will provide you with years of service However always exercise good judgement when you are using this stove You are dealing with FIRE Fire is inherently dangerous and must be treated with respect Stay warm and in good health Respectfully yours SteveVogelzang...

Reviews: