P34AL-15 & P34ALOF-15 Service Manual
TROUBLESHOOTING
9/22/05
8-7
Symptom: Low ice capacity (cont.)
Possible Cause
Possible Remedy
Excessively high head pressure
Check cooling tower or evap condenser to
make sure sufficient water is provided for
cooling and the equipment is operational to
cool the water. Also see “Symptom High Head
Pressure”.
Suction regulator out of adjustment or
defective (optional)
Check the freezer pressure and compare to the
main suction pressure. The suction regulator
should regulate the freezer pressure and create
a 2 psi pressure drop across the valve. Adjust
pressure regulator. Repair or replace defective
valve.
Thawing gas solenoid valve (18) leaking
through during freeze cycle
Check the manual opening stem to make sure it
is in the automatic position (stem screwed in).
Check for leak by sound, temperature
difference and frost during a freeze cycle.
Close the stop valve (90) to confirm suspicion
of leakage. Repair or replace the valve.
Symptom: Poor ice quality
Possible Cause
Possible Remedy
Excessive concentration of solids in the water
tank usually indicated by a build-up of mineral
deposit on the sides and bottom of the tank and
opaque ice production. Also, water
distributors restricted.
Perform a cleaning procedure as well as
removing the freezer cover and cleaning the
water distributors. Make sure the flushing
valve (63) is functioning and the tank overflow
piping is not restricted.
Insufficient water supply indicated by a low
level in the tank
Check water pressure, 40 psig is recommended
minimum. Check for a water line restriction,
partially closed valve, or defective make-up
water float valve. Make sure the water tank
drain is closed.
Water pump rotation wrong direction
Check rotation in relation with arrow on pump
housing and reverse two wires at the motor if
necessary.
Low refrigerant charge, causing an ice out
problem and re-freeze
Check refrigerant level mark on the receiver
and on the painted portion of the gage glass
guard. Be sure to keep the gage glass cocks
closed when finished checking the level.
Suction Pressure to low
Adjust suction regulator valve
Restriction in liquid line, causing short freeze
cycle
Check for closed valve, defective solenoid
valve (20), float switch defective or strainer
restricted. The liquid line will normally have
frost on the down-stream side of a restriction,
especially as the suction pressure decreases.
Summary of Contents for P-34AL-15
Page 1: ...P 34AL 15 P34ALOF 15 TUBE ICE MACHINE Service Manual 5000 9 22 05 ...
Page 2: ......
Page 5: ...9 22 05 ...
Page 8: ......
Page 14: ...P34AL 15 P34ALOF 15 Service Manual TABLE OF CONTENTS vi ...
Page 19: ...P34AL 15 P34ALOF 15 Service Manual INTRODUCTION 9 22 05 1 5 FIGURE 1 2 P34AL 15 Right Side ...
Page 20: ...P34AL 15 P34ALOF 15 Service Manual INTRODUCTION 9 22 05 1 6 FIGURE 1 3 P34AL 15 Left Side ...
Page 22: ...P34AL 15 P34ALOF 15 Service Manual INTRODUCTION 9 22 05 1 8 FIGURE 1 5 P34ALOF 15 Right Side ...
Page 23: ...P34AL 15 P34ALOF 15 Service Manual INTRODUCTION 9 22 05 1 9 FIGURE 1 6 P34ALOF 15 Left Side ...
Page 24: ...P34AL 15 P34ALOF 15 Service Manual INTRODUCTION 9 22 05 1 10 ...
Page 50: ...P34AL 15 P34ALOF 15 Service Manual INSTALLING YOUR TUBE ICE MACHINE 9 22 05 3 24 ...
Page 62: ...P34AL 15 P34ALOF 15 Service Manual START UP OPERATION 9 22 05 5 8 ...
Page 88: ...P34AL 15 P34ALOF 15 Service Manual TROUBLESHOOTING 9 22 05 8 13 ...
Page 130: ...P34AL 15 P34ALOF 15 Service Manual Options and Accessories 9 22 05 10 16 ...
Page 131: ...P34AL 15 P34ALOF 15 Service Manual TABLES CHARTS 9 22 05 11 1 11 Tables Charts ...
Page 138: ...Appendix A ...
Page 141: ......
Page 143: ...i ...
Page 144: ...ii ...
Page 145: ...1 ...
Page 146: ...2 ...
Page 147: ...3 ...
Page 148: ...4 ...
Page 149: ...5 ...
Page 150: ...6 ...
Page 151: ...7 ...
Page 152: ...8 ...
Page 153: ...9 ...
Page 154: ...10 ...
Page 155: ...1 ...
Page 159: ...P24AL P34AL Service Manual INDEX 9 22 05 12 4 ...