05TA Service Manual
INSTALLING YOUR TUBE-ICE
®
MACHINE
3/7/14
3-16
Programming the Electronic Bin Thermostat
The electronic bin thermostat has an LCD readout that displays the temperature in the bin at the sensor.
The control has been preset and locked out at the factory to shut the machine down at 38
°°°°
F and
to re-start at 40
°°°°
F.
The control retains the program even if power is cut to the machine. Under special
conditions, the settings may need to be changed. The lockout switch is located on the inside of the
control. Removal of the four screws on the face of the control will reveal the lock-switch.
Follow the instructions below to reset the switch.
1.
Press the “SET” button to enter the sensors setup mode
2.
Select between “C”- Celsius and “F” - Fahrenheit
Use the up
↑
or down
↓
key to select “F”
3.
Press the “SET” button to set the Set point (S1 will be blinking)
Use the up
↑
or down
↓
key to set the temperature at 38
°
F
4.
Press the “SET” button to set the Differential (DIF 1 will be blinking)
Use the up
↑
or down
↓
key to set the differential at 2
°
F
5.
Select between “C1”- Cooling mode and “H1” - Heating mode
Use the up
↑
or down
↓
key to select “C1”
Machine will shut off when temperature drops to 38
°
F and come on when temperature reaches 40
°
F.
Note:
The sensor will automatically exit the programming mode if no keys are depressed for a period of
thirty seconds. Any settings that have been input to the control will be accepted at that point.
DIGITAL TEMPERATURE
READING
SENSOR
SENSOR POWER
CONNECTION
CONTROL CIRCUIT
CONNECTION
FIGURE 3-9
Electronic Thermostat
Note:
If damaged, the sensor can be replaced without replacing entire unit.
Replacement sensor part #
. Electronic temperature control part #
Sensor cable can be extended up to 400 feet. For more information, consult Tube-Ice
®
Technical Service Department.
Summary of Contents for P118F/HE100
Page 4: ...Vogt Tube Ice Machines Installation Service Manual and Parts Catalog 12A4171M06 05TA Model ...
Page 10: ...05TA Service Manual TABLE OF CONTENTS vi ...
Page 20: ...05TA Service Manual INTRODUCTION 7 19 13 1 10 ...
Page 40: ...05TA Service Manual INSTALLING YOUR TUBE ICE MACHINE 3 7 14 3 18 BLANK PAGE ...
Page 50: ...5 6 5TA Service Manual START UP AND OPERATION 7 19 13 Blank page ...
Page 106: ...05TA Service Manual SERVICE OPERATIONS 3 10 14 9 28 Blank ...
Page 114: ...Blank page ...
Page 115: ...05TA Service Manual TABLES CHARTS 3 10 14 11 1 11 Tables Charts ...