10TA Service Manual
INSTALLING YOUR TUBE-ICE
®
MACHINE
4/14/14
3-9
Ice Machine Model
10TA
Electrical Frequency, Hz.
60
50
Recommended Condenser
BNHS04A029
Total Heat Rejection (BTU/hr)
427,500
393,300
Fans:
Number
HP, Each
Total CFM
4
1 1/2
38,600
4
1 1/2
38,600
Full Load Amps (FLA):
3 ph., 208/230V, 60 hz.
3 ph., 460V, 60 hz.
3 ph., 200V, 50 hz.
3 ph., 380V, 50 hz.
28.0
14.0
--
--
--
--
28.0
14.0
Weight, lbs.:
Net
Shipping
Operating (Maximum flooded) R-404a
1210
1520
1265
Condenser Dimensions, inches (See Fig. 3-7)
A (Width)
B (Length)
C (Height)
D (Leg centerline)
E (Leg centerline)
F (Clearance below)
45.46”
233.16”
49.15”
38”
106.15(3)”
20.5”
Recommended Line Sizes, OD
Liquid
All lengths and orientations
Discharge Gas
Vertical Up, all lengths
Horiz. or Down, < 75 ft.
Horiz. or Down > 75 ft.
1 3/8”
1 5/8”
1 5/8”
2 1/8”
Connections (Condenser):
Liquid (ODF)
Discharge Gas (ODF)
1 3/8”
2 1/8”
1 1/8”
1 3/8”
Connections (Ice Machine):
Liquid (ODF)
Discharge Gas (ODF)
TABLE 3-4
Air-Cooled Condenser Data
Summary of Contents for P18FXT
Page 4: ...Vogt Tube Ice Machines Installation Service Manual and Parts Catalog 12A4171M08 10TA Model ...
Page 10: ...10TA Service Manual TABLE OF CONTENTS vi BLANK ...
Page 20: ...10TA Service Manual INTRODUCTION 4 14 14 1 10 BLANK ...
Page 40: ...10TA Service Manual INSTALLING YOUR TUBE ICE MACHINE 4 14 14 3 18 BLANK PAGE ...
Page 50: ...10TA Service Manual START UP AND OPERATION 4 14 14 5 6 BLANK ...
Page 60: ...10TA Service Manual ELECTRICAL CONTROLS 4 14 14 6 10 BLANK ...
Page 112: ...10 8 10TA Service Manual OPTIONS AND ACCESSORIES BLANK ...
Page 120: ...10TA Service Manual TABLES CHARTS 7 2 14 11 8 BLANK ...