10TA Service Manual
INSTALLING YOUR TUBE-ICE
®
MACHINE
4/14/14
3-12
CONDENSER EQUIVALENT LINE SIZE WORKSHEET
Discharge Gas Line O.D. ___________________
Fitting Type
Number Used
Factor
Total
Globe Valve (open)
Angle Valve (open)
90
°
Elbow
45
°
Elbow
Tee
Feet of Straight Copper Used
Total Fitting Factor
Total Equivalent Feet
Copper Tubing Type “L”
1 1/8” O.D.
1 3/8” O.D.
1 5/8” O.D.
2 1/8” O.D.
Globe valve (open)
28
36
42
57
Angle valve (open)
15
18
21
28
90
o
Elbow
3
4
4
5
45
o
Elbow
1.5
2
2
2.5
Tee (90
°
turn through)
6
8
9
12
Tee (straight through)
2
2
2.5
2.5
2.8
3
3.5
TABLE 3-5
Equivalent Feet Due To Friction
FIGURE 3-6
Minimum Traps For Discharge Lines
*Note: Each recommended line size is based on use of Type “L” copper tubing at a maximum
equivalent distance of 150 feet. See TABLE 3-5 for equivalent feet of valves and fittings.
Summary of Contents for P18FXT
Page 4: ...Vogt Tube Ice Machines Installation Service Manual and Parts Catalog 12A4171M08 10TA Model ...
Page 10: ...10TA Service Manual TABLE OF CONTENTS vi BLANK ...
Page 20: ...10TA Service Manual INTRODUCTION 4 14 14 1 10 BLANK ...
Page 40: ...10TA Service Manual INSTALLING YOUR TUBE ICE MACHINE 4 14 14 3 18 BLANK PAGE ...
Page 50: ...10TA Service Manual START UP AND OPERATION 4 14 14 5 6 BLANK ...
Page 60: ...10TA Service Manual ELECTRICAL CONTROLS 4 14 14 6 10 BLANK ...
Page 112: ...10 8 10TA Service Manual OPTIONS AND ACCESSORIES BLANK ...
Page 120: ...10TA Service Manual TABLES CHARTS 7 2 14 11 8 BLANK ...