10TA Service Manual
TROUBLESHOOTING
4/23/14
8-4
SYMPTOM:
Freeze-up due to extended freeze period.
POSSIBLE CAUSE
POSSIBLE REMEDY
Freezer pressure switch setting too low.
Adjust freezer pressure switch, or replace if
defective. See FIGURE 9-3, Section 9.
Water tank drain valve (39) open or leaking, or
make-up water float valve (12) stuck open.
Close valve, repair, or replace as necessary.
Thawing gas solenoid valve (18) leaking
through during the freeze cycle.
Check the manual opening stem to make sure it
is in the automatic position (stem screwed out).
Check for leakage through the valve by sound
and temperature difference. Close the stop valve
(90) at the receiver to confirm suspicion of
leakage. Repair or replace the valve as needed.
Float switch stuck or failed in the closed
position.
Check to make sure the float switch is opening
and closing.
Liquid feed, “A1” valve stuck open
Check to make sure the “A1” Valve is not in the
manual open position. Disassemble valve and
inspect for debris which could hold the valve
open.
Summary of Contents for P18FXT
Page 4: ...Vogt Tube Ice Machines Installation Service Manual and Parts Catalog 12A4171M08 10TA Model ...
Page 10: ...10TA Service Manual TABLE OF CONTENTS vi BLANK ...
Page 20: ...10TA Service Manual INTRODUCTION 4 14 14 1 10 BLANK ...
Page 40: ...10TA Service Manual INSTALLING YOUR TUBE ICE MACHINE 4 14 14 3 18 BLANK PAGE ...
Page 50: ...10TA Service Manual START UP AND OPERATION 4 14 14 5 6 BLANK ...
Page 60: ...10TA Service Manual ELECTRICAL CONTROLS 4 14 14 6 10 BLANK ...
Page 112: ...10 8 10TA Service Manual OPTIONS AND ACCESSORIES BLANK ...
Page 120: ...10TA Service Manual TABLES CHARTS 7 2 14 11 8 BLANK ...