05TA Service Manual
OPTIONS AND ACCESSORIES
8/13/01
10-14
Power Monitor
All Vogt Tube-Ice machine models are available from the factory with a three phase line voltage
power monitor with LCD display. The units are also available for after market or retrofit installation.
These units monitor line voltage inputs from 190 to 610 volts and provide protection against line
voltage variances that can damage or destroy the compressor motor. Features include automatic
system shutdown and restart based on current line conditions, a voltmeter, and a non-volatile system
memory so settings are retained even if power is lost. If machine is ordered with this option the
power monitor can be factory set to customer specifications. The Vogt Part number for a power
monitor retrofit kit is 12A-7700K010000.
Operation
Parameters
Press Setup Key to enter Setup Mode. Holding the Setup key down for 2 seconds will place all
settings at their defaults. To change settings press the Setup Key repeatedly to step through each
menu item, changing settings where required. As you step through the Setup Menu, the unit will
remain on line, monitoring your system and logging any faults in memory for you to review after you
leave the setup mode. The Setup LED will stay on during setup operations. When you have passed
the last parameter in the setup menu the setup LED will extinguish and you will be returned to the
SYSTEM ON LINE display.
NOTE: The power monitor has no on and off switch so the unit will power up a few seconds after
power is applied.
Nominal Voltage
Set this value at the Incoming Line Voltage. Use the arrow keys to change voltage. 190 - 610
Voltage Adjustment. Default voltage is 208.
Voltage Range
Use the arrow keys to set the under/over percentage (2 to 25%) of incoming voltage. This will turn
off equipment for a specified time if incoming voltage exceeds set percentage. The recommended
voltage range is 10%. Default is 10%.
Delay On Break
Ranges from Off to 10 minutes in .1 minute increments. Use the arrow keys for adjustment. “Delay
On Break” is energized when the Load Relay is deactivated, and the load will remain off until the
specified time has elapsed. Default is .5 minute.
Delay On Make
Ranges from Off to 10 minutes in .1 minute increments. Use the arrow keys for adjustment. “Delay
On Make” is energized when the control voltage is reactivated, and the load will remain off until the
specified time has elapsed. Default is .1 minute.
Summary of Contents for TUBE-ICE 05TA
Page 4: ...Vogt Tube Ice Machines Installation Service Manual and Parts Catalog 12A4171M06 05TA Model ...
Page 82: ...05TA Service Manual SERVICE OPERATIONS 8 13 01 9 18 FIGURE 9 10 Cutter Drive Parts ...
Page 95: ...05TA Service Manual OPTIONS AND ACCESSORIES 8 13 01 10 11 FIGURE 10 3 Control Panel Parts ...
Page 97: ...05TA Service Manual OPTIONS AND ACCESSORIES 8 13 01 10 13 FIGURE 10 4 Wiring Schematic ...
Page 103: ...05TA Service Manual TABLES CHARTS 8 14 01 11 1 11 Tables Charts ...