27
Table 3 Charge Mode Specifications
Utility Charging Mode
Model
5KVA with 2 MPPTs
5KVA with 3 MPPTs
Charging Current (UPS)
@ Nominal Input Voltage
2A/10A/20A/30A/40A/50A/60A
Bulk Charging
Voltage
Flooded Battery
58.4
AGM / Gel Battery
56.4
Floating Charging Voltage
54Vdc
Charging Algorithm
3-Step
Charging Curve
Time
Battery Voltage, per cell
Charging Current, %
100%
50%
Bulk
(Constant Current)
Absorption
(Constant Voltage)
Maintenance
(Floating)
Current
Voltage
T1
T1 = 10* T0, minimum 10mins, maximum 8hrs
T0
2.43Vdc (2.35Vdc)
2.25Vdc
Solar Charging Mode
Model
5KVA with 2 MPPTs
5KVA with 3 MPPTs
MPP tracker numbers
2
3
Charging Current
2 x 60 Amp
3 x 60 Amp
Max. PV Array Open Circuit Voltage
145Vdc
PV Array Voltage High Loss
145Vdc
PV Array Voltage High Comeback
140Vdc
PV Array Voltage Low Loss
Battery v 1V
PV Array Voltage Low Back
Battery v 2V
PV Array MPPT Voltage Range
60~115Vdc
Min. PV Voltage
34Vdc
System Voltage
48Vdc
Maximum operating PV input current
50A
Isc PV
60A
Max. inverter backfeed current to
array
0A
Standby Power Consumption
2W
DC Voltage Accuracy
+/-0.3%
PV Voltage Accuracy
+/-2V
Charging Algorithm
3-Step
DC Reverse Polarity Protection
Yes