20
CHE is default setting.
13: Battery voltage calibration
Interface
Setting
Parameter 2:
Select “
Add
” or “
Sub
” function to adjust battery
voltage to real figure.
Parameter 3:
the voltage range is from 0V to 9.9V and the
default value is 0V.
14: Charger voltage adjustment
Interface
Setting
Parameter 2:
you may choose
Add
or
Sub
to adjust charger
voltage
Parameter 3:
the voltage range is from 0V to 9.9V and the
default value is 0V.
NOTE:
*Before making voltage adjustment, be sure to disconnect all
batteries first to get the accurate charger voltage.
* Any modification should be suitable to battery specifications.
15: Inverter A voltage adjustment
Interface
Setting
Parameter 2:
you may choose
Add
or
Sub
to adjust inverter A
voltage.
Parameter 3:
the voltage range is from 0V to 9.9V and the
default value is 0V.
16: Inverter B voltage adjustment
Interface
Setting
Parameter 2:
you may choose
Add
or
Sub
to adjust inverter B
voltage*.
Parameter 3:
the voltage range is from 0V to 9.9V and the
default value is 0V.
*It will display number 1 under
or
to represent
the voltage of inverter B.
17: Inverter C voltage adjustment
Interface
Setting
Parameter 2:
you may choose
Add
or
Sub
to adjust inverter C
voltage*.
Parameter 3:
the voltage range is from 0V to 9.9V. The default
value is 0V.
*It will display number 2 under
or
to represent
the voltage of inverter C.