10
3.
Installation
3.1
Basic requirement
Ambient temperature: 0°C~+55°C
Storage temperature: -15ºC ~ 60ºC
Relative humidity: 5% ~ 95%
Altitude: If the UPS is installed within 1000m, the UPS power will not be derated.
When the height is over 1000m, the output power will be derated by following the
table.
Altitude(m)
1000
1500
2000
2500
3000
3500
4000
4500
5000
Coefficient
100%
95%
91%
86%
82%
78%
74%
70%
67%
Vertical: No vibration and the degree of deviation from vertical shouldn’t be more
than 5°.
Space: It’s requested to have a clearance of approx. 80 cm to the front and back of
the unit and approx. 20 cm to the side.
Minimum 80cm
Minimum
20cm
Minimum 80cm
Minimum
20cm
The UPS should be installed in the environment with free ventilation, less dust, optimum
ambient temperature and humidity.
The recommended ambient temperature is 20°C~25°C with 50% humidity.
Caution!
It’s NOT allow to have flammable, explosive or corrosive gas or liquid in
installation environment. It is forbidden to install in a metal conductive dust
environment.