15
The recommended sizes of the ring terminals are listed as below:
Items
30K/40K
60K/80K
AC INPUT/ BYPASS/
OUTPUT/BATTERY
AC INPUT/ BYPASS/
OUTPUT
BATTERY
D (mm)
8.4
8.4
10.5
L (mm)
16
16
22
Torque (Nm)
4.5
4.5
9
After connecting all the cables, please double check the issues as below:
Check the phase sequence of LINE INPUT, BYPASS and OUTPUT.
Check the polarity of the battery cables.
Make sure all the connected cables are screwed tightly.
4.2
Communication
The UPS provides a variety of communications. The details are listed as below:
EPO
Dry contact
Output
Iutput
Intelligent slot
4.2.1
Intelligent slot
The intelligent slot can provide SNMP solution for remote monitor. Please request the
supplier for detail information.
4.2.2
Dry contact
There are 6 output and 2 input dry contacts. The detailed functions are listed as below.