33
Advanced
LCD Screen
Description
It’s required to enter password (4 digits) to access the
“ADVANCED”. The default password is “
0000
”.
If entered password is right, the page will jump to setting
screen. If the password is wrong, it will ask to enter again.
1.
OP rated voltage:
Select the output rated voltage. There
are three options, 220Vac, 230Vac and 240Vac. 220Vac is
default setting.
2.
OP Frequency:
Select the output frequency
50Hz:
The output frequency is setting for 50Hz.
60Hz:
The output frequency is setting for 60Hz.
50Hz is default setting.
3.
CVCF status
(constant voltage and constant frequency
function)
En :
CVCF function is enabled. The output frequency will
be fixed at 50Hz or 60Hz according to setting of “OP
Freq.”. The input frequency could be from 40Hz to 70Hz.
Dis:
CVCF function is disabled. The output frequency will
synchronize with the bypass frequency within 45~55 Hz
for 50Hz system or within 55~65 Hz for 60Hz system.
Disable is the default setting.
4.
Line Voltage range:
Set the acceptable line input voltage
range.
L:
Low voltage point for line voltage. The setting range is
176V ~ 205V. 176V is default setting.
H:
High voltage point for line voltage. The setting range is
235V ~ 265V. 265V is default setting.
5.
Line Frequency range:
Set the acceptable line input
frequency range.
L:
Low frequency point for line voltage. The setting range
is 45Hz ~ 49Hz for 50Hz system and 55Hz ~ 59Hz for 60Hz
system. 46Hz is default setting for 50Hz system and 56Hz
is default setting for 60Hz system.
H:
High frequency point for line voltage. The setting range
is 51Hz ~ 56Hz for 50Hz system and 61Hz ~ 66Hz for
60Hz system. 54Hz is default setting for 50Hz system and
64Hz is default setting for 60Hz system.
USER
Password:
0000
USER
OP rated Volt:220
OP Freq.(Hz) :50.0
CVCF status:Dis
Line Voltage Range:
L:176V H:265V
Line Freq.Range:
L:46Hz H:54Hz
1/5