26
5. INSTALLATION.
•
Rea
d and respect the Safety Information, described in
section 2 of this document to obviate some of the stated
indications which may cause a serious or very serious
injuries to persons in direct contact or in the vicinity as
well as break-downs in the equipment and/or loads
connected to itself.
• Unless the opposite is indicated, any action, indications,
premises, notes and others, are applicable to UPS equipment,
no matter it may belong to a parallel system or not.
5.1. RECEPTION OF THE EQUIPMENT.
•
It i
s dangerous to handle the equipment over the pallet
without much prudence, because it could overturn and
cause serious or very serious injuries to the operators if
any fall and/or trapping occurs. Pay attention to section
«
2.2.3.1. To keep in mind
»
as regards to handling,
moving and location of the unit.
• Use the most suitable medium to move the packaged UPS,
with a pallet truck or fork lifter.
• Pay attention to the weights of handling equipment according
to the model stated in the technical specifications in section «9.
Annexes».
5.1.1. Reception, packaging and contents.
• Recepti
on. To check:
Data label stuck on the package corresponds to the ones
stated in the purchase order. Once the UPS is unpacked,
check the purchasing details with the one in the nameplate
of the equipment, stuck at the back of the front door
(PF)
.
If any discrepancies exist, make the nonconformity as
soon as possible, by quoting the serial number of the
equipment and the references of the delivery note.
No incident has happened during the transport (packaging
and impact indicator are in perfect status). Otherwise,
follow the protocol stated in the label attached to the
impact indicator, located on the packaging.
• Unpacking.
Check the content before deserting the packaging.
Unpack the package according to the
«Unpacking»
procedure in the supplied document, including the manual
and/or attached CD.
• Contents.
Standard equipment up to 20 kVA (LV) / 40 kVA (HV): CD,
manual and battery fuses.
Standard equipment > 20 kVA (LV) / 40 kVA (HV): CD
and manual.
Battery cabinet: Fuses and cable connection bundle of
3.5m. length and suitable cross section.
If the UPS belongs to a parallel system: A
communication cable bundle per equipment.
• Once the reception is finished, it is advisable to pack the UPS
again till its commissioning in order to protect it against
mechanical impacts, dust, dirt, etc.
• The packaging of the equipment has a cardboard pallet or
wooden type depending on the case, expanded polystyrene
corners, bag and polyethylene strip, all of them are recyclable
materials. When it is required to dispose them, do it in
accordance to the regulation in force.
It is advisable to keep the packaging for 1 year as minimum.
5.1.2. Storage.
• The storage of the
equipment should be in a dry and cool place,
and protected from rain, dust, water jets or chemical
agents. It
is advisable to keep each equipment and battery set inside
their origin
al packaging because it is designed to assure the
best protection during transport ant storage.
•
In general, less particular cases, the UPS has sealed lead
acid batteries and their storage must not exceed 6
months without recharging them (see last section of
charge, the label stuck in the packaging of the equipment
or battery set).
Lapsed this period of 6 months, connect the equipment to
mains together with the battery set if any, paying attention
to the safety instructions and connection.
Models with separate static bypass line is not necessary
to connect with this power terminal st
rip.