23
Adjustable parameters
NOTE:
VODIA is used to adjust parameters in CIU
and EMS2. Some parameters require special authori-
zation.
Functions
Primary control mode
Selects which regulator is to be used when there is no
primary control switch.
Alternative position ............................. “Isochronal” or
“droop” characteristic
Preset position ..................................... “Isochronous”
Control gradient
(Droop)
Determines the engine speed droop to be used (gradi-
ent)
Min. value ........................................................... 0 %
Preset value ........................................................ 4 %
Max. value .......................................................... 8 %
Lamp test
This parameter determines if a lamp test is to be per-
formed when the system is started.
Alternative position ............................... “Off” or “On”
Preset position .................................................. “On”
Idle.
Sets the idle speed.
Min. value
600 rpm
Preset value
900 rpm
Max. value
1200 rpm
Pre-heating before ignition
Selects if pre-heating is activated directly when the ig-
nition is turned on. If the parameter “Off” has been se-
lected, pre-heating must be activated manually via the
ignition lock or pre-heater button.
Alternative position ............................... “Off” or “On”
Preset position ................................................... “Off”
Connected to system voltage during
running/stop, EMS
Stops input data to the CIU unit connected to system
voltage at “run” or “stop”.
Preset position ................................................. “Stop”
Connected to system voltage during
running/stop, CIU
Stops input data to the CIU unit connected to system
voltage at “run” or “stop”.
Preset position ................................................. “Stop”
Idle voltage, CIU
Voltage of the throttle signal corresponding to idle at
the CIU unit.
Min. value ......................................................... 0.3 V
Preset value .................................................... 1.17 V
Max. value ........................................................ 1.9 V
Voltage max. rpm CIU
Voltage of the throttle signal corresponding to full
throttle at the CIU unit.
Min. value ......................................................... 1.9 V
Preset value ...................................................... 4.5 V
Max. value ........................................................ 4.7 V
Alarm limits
Alarm limit, high coolant temperature
a warning lamp is lit at this temperature.
Min. value ......................................................... 95 °C
Preset value .................................................... 104 °C
Max. value ...................................................... 103 °C
Parameter settings
Summary of Contents for TAD734GE
Page 1: ...EMS 2 Industrial engines TAD734GE Installation 1 1 I ...
Page 2: ......
Page 13: ...General information 11 Wiring diagram EMS 2 engine cable harness ...
Page 45: ...43 References to Service bulletins Group No Date Concerning ...
Page 46: ... Notes ...
Page 48: ...7747352 English 10 2009 ...