Component

Picture

Function

Optional/Required

If Not Used...

PS914

24 VDC power supply

Power transfer

(EPT-10 shown)

External horn

Building fire alarm

(normally closed contacts)

External inhibit device

(card reader, key switch, etc.)

Rim and vertical -

(normally closed contacts)

Door position switch

(normally closed contacts)

Supplies power to Chexit

Provides louder alarm than

Chexit internal horn

Unlocks Chexit in case

of fire alarm

Arms Chexit 2.5 seconds

after door closes; sounds

alarm if door forced open

Allows authorized egress

or ingress without alarm

Transfers electrical power

through frame to door

(wires concealed)

Required

Insulate blue and

brown wires

separately

Required

Connect orange

wire to white

wire

Connect green

wire to

white wire

Use door loop or

electric hinge

Required

(Von Duprin PS914)

Highly

recommended

Optional

Required

Optional (wire multiple

external inhibit devices

in series)

Optional

Used?

Yes

Yes

Table 1. Installation Components

Table 2. Wiring Requirements

Wiring

Type of Power

Transfer

(door to frame)

Maximum Wire

Length from Power

Supply to Power

Transfer

Minimum

Wire Gauge

Power Supply Input

Power Supply Output

(+24 and GND)

External Alarm, Fire Alarm,

Door Position Switch,

External Inhibit Device

EPT-10

EPT-10

Electric Hinge

Electric Hinge

EPT-10,

Electric Hinge

N/A

Per code

100 feet

200 feet

75 feet

150 feet

Per code

14 GA

12 GA

14 GA

12 GA

18-22 GA

Not critical

The wiring requirements in Table 2

above 

must

 be followed.

IMPORTANT

!

E7500 Electric Mortise Lock

Serves as locking device on

CXE9975 mortise applications

Optional

(for CXE9975)

Yes

Table 3. Wire Functions

Power 24 VDC

Common for NO output;
24 VDC, 1 A maximum

Normally open output;
closes during alarm

Communication line;
used to connect Chexits

Communication line;
used to connect Chexits

Fire alarm input;
0 VDC = fire,
24 VDC = no fire

Door position switch input;
0 VDC = door open,
24 VDC = door closed

External inhibit input;
0 VDC = Chexit inhibited,
24 VDC = Chexit active

Signal 24 VDC;
can be used to power
FA, DPS, and EI inputs

Power supply ground

Red

Blue

Brown

Violet

Gray

Yellow

Orange

Green

White

Black

+24

C

NO

CM-

CM+

FA

DPS

E  I

SC

GND

Optional

(for CXE9975)

Electric Mortise Fail safe -

(normally closed contacts)

Electric Mortise Fail secure -

(normally open contacts)

Allows authorized egress

or ingress without alarm

Allows authorized egress

or ingress without alarm

Optional (wire multiple

external inhibit devices

in series)

Optional (wire multiple

external inhibit devices

in parallel)

FIRE

Summary of Contents for CX33A

Page 1: ...RNING GENERAL INFORMATION ELECTRICALSPECIFICATIONS Voltage 24 VDC Current Chexit 0 4 A Current Electric mortise 0 3 A Current on arming 300 mS 16 A in rush External alarm dry contacts NO and C 24 VDC 1 A rating Normally closed inputs Fire alarm FA required External inhibit EI Door position switch DPS The Von Duprin Chexit device is designed for accident hazard or fire exit applications It meets bo...

Page 2: ...ble 1 3 Determine the physical location of each component used see Figure 1 4 and 6 4 Pull field wiring between component locations and frame side of power transfer see Figure 1 4 and 6 5 Mount components and connect them to field wiring see Figure 2 3 5 or 7 6 Connect field wiring to frame side of power transfer Route wires through frame back box 7 Install frame back box and frame side of power t...

Page 3: ...and GND ExternalAlarm Fire Alarm Door Position Switch External Inhibit Device EPT 10 EPT 10 Electric Hinge Electric Hinge EPT 10 Electric Hinge N A Percode 100 feet 200 feet 75 feet 150 feet Percode 14 GA 12 GA 14 GA 12 GA 18 22 GA Not critical The wiring requirements in Table 2 above must be followed IMPORTANT E7500ElectricMortiseLock Servesaslockingdeviceon CXE9975mortiseapplications Optional fo...

Page 4: ...ly closed contact Normally closed contact Red 24 Blue C Brown NO Violet CM Gray CM Yellow FA Orange DPS Green El White SC Black GND Cable to Chexit device Normally closed contact Red 24 Blue C Brown NO Violet CM Gray CM Yellow FA Orange DPS Green El White SC Black GND Power transfer Cable to Chexit device In this double door application both doors open in the same direction and each is equipped wi...

Page 5: ... x E7500 FS Mortise Lock DPS Junction box External alarm EPT External inhibit Red 24 Blue Brown NO Violet CM Gray CM Yellow FA Orange DPS Green EI White SC Black GND Violet White Black Black Power transfer 24 GND Not used insulate separately FIRE Normally closed contact Normally closed contact Normally open contact PS914 power supply 120 240VAC 2AMP Cable to Chexit device E7500 Electric mortise lo...

Page 6: ...move backing from sign and put sign on door above Chexit device sign is in cardboard tube 9 Go to Operation for testing and troubleshooting Cable inside end cap bracket Orient cylinder as shown or unit will not operate CAUTION INSTALLATION Slide module into cover plate as shown 1 With end cap and cover plate removed drill 5 8 diameter wire access hole in surface of door 2 3 Route Chexit cable thro...

Page 7: ...reen and white wires 2 If external inhibit not used connect green and white wires together Red LED does not light Power not reaching Chexit Replace reset AC fuse circuit breaker check power supply input output voltages check input voltage at Chexit cable connector Red LED on solid then flashes fast andhornsounds 1 Pushpadpressed 2 Pushpadswitchdisconnected 1 Releasethepushpad 2 Connect pushpad swi...

Page 8: ...a door position switch is used the Chexit arms 2 5 seconds after the door closes 6 If you are using a door position switch but you want the full rearm time to expire before the Chexit arms call Technical Support at 1 877 671 7011 7 For proper operation the rearm time of each ganged Chexit must differ by at least 2 seconds Location of Chexit option switches OPTIONS Factory settings shown 8 Off 7 Of...

Reviews: