931001-00

Notes: Deadbolt will not function with this strike. Check with factory for retrofit applications.

For lock or device preparation, see their directions.

Prepare frame for strike (see other side).

Wire strike (Figure 1). (Switches on 6210DS only.)

Install insert for auxiliary bolt operation (Figure 2).

Test strike: Apply solenoid power. Fail secure (FSE) lip unlocks. Fail safe (FS) lip locks. Figure 1 shows status of switches.

6  Install strike with two #12-24 screws. Make sure clearance between latch bolt and strike lip is 1/32” (Figure 3). If not, uninstall strike, adjust (Figure 4), 

and reinstall.

Test door: With strike unlocked, door opens with latch bolt extended. When door closes, latch bolt rides over strike lip.

Figure 1

Figure  3

Top view;

faceplate not

shown for clarity

1/32”

Latch bolt

Strike lip

Figure  2

Insert and location

for Von Duprin

mortise locks

Insert and location

for Schlage

mortise locks

Insert and location

for Yale, Best, and

Sargent mortise

locks

Figure  4

A

B

C

To adjust strike, loosen screws

A, B, and C and move backbox

sideways as necessary

DC input is

 

nonpolarized

NOTE

J1

P1

P1 J1A

P1A

SO-12 or SO-24

   

12 VDC

or

24 VDC

12 VAC            SO-12      12 VDC

    

or

24 VAC           SO-24      24 VDC

 

{

{

Wiring

for DC

supply

Wiring

for AC

supply

Solenoid

Use crimp

connectors to

splice field wiring

to P1 leads

Yellow solenoid wires: 12 VDC, 0.57 A

 

 

 

 

 

Black solenoid wires: 24 VDC, 0.29 A

 

 

   

 

 

(also shown on strike label)

 

   

 

SOLENOID POWER REQUIREMENTS

 

 

Use crimp connectors to

splice field wiring to P2

leads; insulate unused leads

Switches shown with tripper

depressed, strike lip closed and locked

(switches  and  tripper  on 6210DS only)

J2

Fail  safe  (FS)

J2

Fail secure  (FSE)

S1

S2

1
2
3
4
5
6

S1

S2

1
2
3
4
5
6

Standard:  5  A,  30  VDC

Gold:  0.25 A,  30  VDC

SWITCH RATINGS

}

P2

Red (C)
Blue
Yellow
White (C)
Gray
Violet

}

S1

(monitors

tripper)

S2

(monitors

strike lip)

J2 P2

NOTE:

Static Strength Rating 1500 lb.

Dynamic Strength Rating 70ft.-lb.

Endurance Rating 250,000 c.S

89/336/EEC

Electric Strike Single Door Mortise Application

6210/6210DS

Installation Instructions