39
ENGLISH
HEAT EXCHANGER, CONDENSE TRAY REMOVAL AND SERVICING
Disconnect the flexible pipe from the condense adapter, be aware the condense pipe may contain water.
Withdraw the heat exchanger and condense tray assembly by pulling on the securing strap and remove from the unit. Take
care to avoid damaging the heat exchanger air passages. See Figure 17 & 18.
Be aware, the condensate tray may contain water.
Check all the air passages in the heat exchanger are free from obstruction. If not clean by acuuming or with a light brush.
NOTE:
DO NOT USE WATER OR ANY OTHER FLUIDS.
NOTE:
Under no circumstance must any sharp implements which are likely to distort or puncture the heat exchanger air
passage walls, be used.
Wipe clean the condensate tray.
Figure 17. Removing
heat exchanger &
condensate tray
SERVICING CARRIED OUT WITH FANS IN PLACE (recommended)
Remove all dust etc. from both the impellor and the motor, taking care not to disturb the balance of the fan.
Refit or replacement is in reverse order.
FAN CASE ASSEMBLY REMOVAL & SERVICING
Referring to section 13.3 to 13.7 remove the heat exchanger and condense tray assembly. Remember there may be water
in the condensate tray.
Disconnect the PCB board and fan cables from the terminal.
Push the twin fan case assembly towards the void and down
to remove.
Clean fans through the holes in the casing where necessary, use a soft
brush or vacuum.
Figure 18. Mains cover plate & fan assembly
TERMINAL
19
17
HEAT
EXCHANGER
AIR PASSAGES
FAN
ASSEMBLY
MAINS SUPPLY
COVER PLATE
18
Figure 19 Slide back and down to remove
Summary of Contents for HRI MINI
Page 22: ...22 ITALIANO SCHEMA ESPLOSO Figura 21 Schema esploso HRI MINI 21...
Page 42: ...42 ENGLISH EXPLODED DIAGRAM Figure 21 HRI MINI exploded diagram 21...
Page 62: ...62 MAGYAR ROBBANTOTT BRA 21 bra HRI MINI robbantott bra 21...
Page 82: ...ESPA OL VISTA EN DESPIECE ORDENADO Figura 21 Vista despiezada 21 82...
Page 85: ...Note...