47
Register 51:
State of output regulation CO2 On/off (state of alarm) [only read].
- 0: Output dissabled (relay contact open). No alarma.
- 1: Output activada (relay contact closed). Alarm.
Output On/off by potential-free relay contact. Output “Regulation CO2” On/off.
Register 52:
State of output regulation CO2 proportional [only read].
The value that is sent is the value of the output percentage (0% to 100%) In binary 16 bits.
Analogic proportional Output 0…10V: Output “Regulation CO2” proportional.
Register 53:
Remote stop [only read].
- 0: Remote stop disabled (open digital input).
- 1: Remote stop activated (digital input closed).
Register 54:
Temperature [only read].
The value that is sent is the temperature value (0.0ºC to 50.0ºC) multiplied by 10 In binary 16 bits.
0,0ºC 0x0000
50,0ºC 0x01F4
Temperature sensor integrated in the regulator.
All / nothing output
Register 51
Hysteresis [ppm]
Register 6
Setpoint CO2 [ppm]
Register 3
CO2 [ppm]
Register 30
Proportional output [%]
Register 52
Maximum output [%]
Register 10
Minimum output [%]
Register 9
Proportional band[%]
Register 7
Integration time [s]
Register 8
Setpoint CO2 [ppm]
Registro 3
CO2 [ppm]
Registro 50
ENGLISH