41
NO FROST
This is the variable that defines the possible strategies for NO FROST operation. The possible values are:
UN-BALAN.: flow unbalancing; note: this option must be deactivated in order for the appliance to comply with standard
PASSIVHAUS and preheater installed.
HEATER: pre-heater; note: this option must be activated in order for the appliance to comply with standard PASSIVHAUS.
HEAT FORC.: in the case that the pre-heater strategy is activated, this permits the installer to control pre-heater operation,
switching it on for 15 s
Pre-set default values :
UN-BALAN: Not enabled
HEATER: Not enabled
POSTHEAT
The variable that controls activation of the post-heater, if present. The editable default value is: NO.
POSTTEMP
The variable that defines the threshold temperature value, over which the post-heater switches on, if present. The editable
default value is: 16°C.
ENGLISH
INSTALL
NO FROST
POSTHEAT
POSTTEMP
NOFROST
UN-BALAN.
HEATER
HEAT
FORC.
INSTALL
NO FROST
POSTHEAT
POSTTEMP
POSTHEAT
YES
INSTALL
NO FROST
POSTHEAT
POSTTEMP
POSTHEAT
16
Summary of Contents for VORT HR 450 Avel D
Page 3: ...3 Vortice ZH 142 142 144 145 147 148 149 151 164...
Page 142: ...142 Vort HR 450 Avel D EC 85 Vortice 8 Vortice Vortice Vortice...
Page 143: ...143 45 C 3mm III M 220 240V 230V A 1 1 A...
Page 145: ...145 6 7 8 160mm 5 5a 5a 6 h 50 mm 60 mm 7 8...
Page 146: ...146 9 10 11 12 9 10 10 11 11 12 12...
Page 151: ...151 3 A B 1 2 T Ext T Int T Exh T Sup 3 4 OFF 1 2 3 Boost 5 6 A B 1 2 3 4 5 6...
Page 163: ...163 INFO S 0 9 6 6 M 0 9 6 4 CFG 6 4 MAIN MENU ALARM SETUP INFO...
Page 164: ...164 16 17 18 6 19 19A 17 17 18 18 16 16 19 19 A...
Page 165: ...165...
Page 180: ...180 Note...
Page 181: ...181 Note...
Page 182: ...182 Note...
Page 183: ...183 Note...