NEVO+600 Series
INSTALLATION MANUAL
_____________________________________________________________________________________________________
Page 1 of 4
Vox Power Limited | Unit 2, Red Cow Interchange Estate, Ballymount, Dublin 22, D22 Y8H2, Ireland | T +353 1 4591161 |
PLEASE READ THIS INSTALLATION MANUAL CAREFULLY BEFORE INSTALLING THIS PRODUCT AND KEEP THIS MANUAL FOR FUTURE REFERENCE.
All specifications are believed to be correct at time of publishing. Vox Power Ltd reserves the right to make changes to any of its products and to change or improve any part of the specification,
electrical or mechanical design or manufacturing process without notice. Vox Power Ltd does not assume any liability arising out of the use or application of any of its products and of any information
to the maximum extent permitted by law. No license, express or implied, by estoppel or otherwise, to any intellectual property rights is granted by this document or by any products of Vox Power Ltd.
VOX POWER LTD DISCLAIMS ALL WARRANTIES AND REPRESENTATIONS OF ANY KIND WHETHER EXPRESS OR IMPLIED, INCLUDING, BUT NOT LIMITED TO, IMPLIED WARRANTIES OF SUITABILITY, FITNESS
FOR PURPOSE, MERCHANTABILITY AND NONINFRINGEMENT.
Please consult your local distributor or Vox Power directly to ensure that you have the latest revision before using the product and refer to the latest relevant user manual for further information relating
to the use of the product. Vox Power Ltd products are not intended for use in connection with life support systems, human implantations, nuclear facilities or systems, aircraft, spacecraft, military or
naval missile, ground support or control equipment used for the purpose of guidance navigation or direction of any aircraft, spacecraft or military or naval missile or any other application where product
failure could lead to loss of life or catastrophic property damage. The user will hold Vox Power Ltd harmless from any loss, cost or damage resulting from its breach of these provisions.
Important installation information
This NEVO+600 series of configurable power supplies are intended for use within end customer applications which restrict access to un-authorized personnel. The instructions in this manual and all
warning labels on the product must be adhered to carefully.
SAFETY
The NEVO+600S/SL and NEVO+600M/ML series are designed in accordance with the relevant safety requirements of IEC/EN/UL/CSA 62368-1, IEC/EN/UL/CSA
60950-1, IEC/EN/UL/CSA 60601-1, Low voltage Directive LVD 2014/35/EU and EMC directive EMC 2014/30/EU. All NEVO+600 series power supplies must be
installed correctly in a controlled environment which restricts access to any un-authorised personnel. Equipment and system manufacturers must protect
service personnel against unintentional contact with the output terminals.
HAZZARDS
Dangerous voltages are present within the power supply.
It should only be handled by qualified personnel when the power supply has been disconnected from the mains supply voltage for more than 3 minutes.
External surfaces of the power supply may become extremely hot during and after operation. Appropriate care should be taken. If series and/or parallel
combinations of outputs exceed safe voltage and/or energy levels, the final equipment manufacturer must provide the appropriate protection for both users
and service personnel.
DE-RATINGS
Ambient
Temperature
•
The input module power must be de-rated by 2.5%/°C above 50°C ambient up to a maximum ambient temperature of 70°C.
Input Voltage
•
Standard & Medical (S/M) - The input module power must be de-rated by 4.28W/V
RMS
below120 V
RMS
(600W @ 120 V
RMS
, 450W @ 85 V
RMS
)
•
Low Noise (SL/ML) - The input module power must be de-rated by 3.21W/V
RMS
below120 V
RMS
(450W @ 120 V
RMS
, 338W @ 85 V
RMS
)
Remember to take the appropriate de-rating into consideration before specifying any NEVO+600 power supply for an application.
If in any doubt, please contact Vox Power directly or your local Vox Power representative.
HEALTH AND SAFETY
To comply with section 6 of the health and safety at work act, a label that is clearly visible to service personnel must be placed on the final equipment. These
labels warn that surfaces of the power supply may be hot and should not be touched when the product is operating.
FUSING
The power supply has internal single pole fusing in the L (Live) line.
Fuses are not replaceable. Damaged units should be returned to Vox Power for analysis and repair.
For Medical (60601-1) installations, the end application should provide an appropriately rated external fuse in the Neutral line.
DC operation is not covered by safety approvals. Contact Vox Power for details.
SERVICING
The power supply contains no user serviceable parts. Repairs must be carried out by authorised personnel only.
Contact Vox Power for further information.
APPROVAL
LIMITATIONS
NORTH AMERICA - When this product is used with 180V
AC
–253V
AC
mains where no neutral is present, connect the two live wires to L (Live) and N (Neutral) on the
input connector.
COOLING
For proper cooling of the power supply, the air intake and outlet must not be impeded. Allow 50mm clearance at both ends and position cabling appropriately.
EARTH TERMINAL
MARKING
To comply with the requirements of IEC/EN/UL/CSA 62368-1, IEC/EN/UL/CSA 60950-1 & IEC/EN/UL/CSA 60601-1, where the incoming wiring earth is intended
for connection as the main protective earth conductor and where the terminals for such a connection is not supplied on a component or subassembly, the user
shall add an appropriate label displaying a protective earth symbol in accordance with IEC60417-5019 (2006-08)
directly adjacent to the terminal. The label
should be durable and legible and should withstand the 15 second rub test as per UL60950-1 section 1.7.15.
WARRANTY
Contact your sales agent or Vox Power for product repairs. See Vox Power standard terms and conditions for warranty conditions.
PRODUCT LABELS
The external product label contains information relevant to the power system. The label contains input voltage, maximum input current, input frequency,
maximum output power, fuse rating and type, serial number, approvals and product part number in form NEVO+600xx-yyyy-zzz.
NEVO+ OUTPUT
MODULES
Each output module label contains information relevant to that output. The label contains voltage adjustment range, maximum output current, serial number,
approvals and the part number in format OPx.
OTHER
•
A label warning that external surfaces are hot during operation and that the unit should be allowed to cool down properly should be placed on the unit
where such a label is clearly visible.
•
The NEVO+600 series is designed to comply with EMC standards but it does not imply that the end system will comply.
•
To prolong the life of the unit, use in dust free environment.
•
Units can sometimes be damaged during transit. In the event of transit damage, DO NOT connect power to the unit. Contact your sales agent or Vox
Power.
•
Always use adequately sized cables and ensure good crimp connections. Use cable supports to minimise stress on connectors.
•
Avoid excessive shock or vibration.