38
The above figure shows that 5 detectors are registered in the original setting, but only 2
detectors are on-line currently; 10 modules are registered, but only 7 modules are on-line. The
figure also prompts warning messages, such as "Press OK to enter setup interface" and
"register and production type address will be changed", to prompt the user to make choice.
When auto register is in process, the time countdown will be displayed at the bottom of the
screen. If current interface board is under communication, time-out error will occur when
counting down to 0, and the system prompt is as follows:
Figure 4-51 Time-out error of auto register
Auto register of the system may rewrite the system setting; proceed with
caution!
4.4.5 Isolate current alarm
The function of this menu item is exactly the same as that of "isolate" on the panel.
4.4.6 Query current isolation
The following form interface will pop up on the screen after selecting this menu item:
Figure 4-52 Query current isolation
The entire screen can display 8 isolating points; if the total number exceeds 8, click on
P
REV
P
AGE
and
N
EXT
P
AGE
to turn page and inquire. Click on
R
ETURN
button to exit the
isolation query interface.
The isolation query interface is for the user to acknowledge current isolation condition of
the equipment; the interface is not provided with rewriting function. It means the properties of
detector/module cannot be changed at this interface.
4.4.7 Cancel all isolation
Click on this menu item and the system will cancel the isolating operation. The system will
automatically search for all bus points isolated and cancel all isolating marks.
This function offers a convenient way for the user to cancel isolating setting. If the isolation
of individual point is required to be cancelled, enter into detector/module setup interface and
rewrite corresponding isolating marks in the form.