VTI Instruments Corp.
56
EX2500A Web Page Operation
IP
C
ONFIGURATION
The
IP Configuration
page contains information concerning network configuration information
and IP address options.
F
IGURE
5-5:
IP
C
ONFIGURATION
P
AGE
(D
EFAULT
S
ETTINGS
S
HOWN
)
•
IP Source
: the IP address for the EX2500A is determined by one of three sequenced
mechanisms:
DHCP
→ AutoIP → Static
. If an IP address cannot be obtained with the first
mechanism, it will progress to the next method. The user also has the ability to enable or
disable either of these methods by utilizing the adjacent checkboxes.
o
DHCP
: a protocol that obtains an IP address automatically if the EX2500A is connected
to a network with a DHCP server. By default, the EX2500A will attempt to locate a
DHCP server. If one is found, the IP address assigned by the DHCP server will be
assumed. Otherwise, after a timeout of 20 seconds, the unit will attempt to obtain an IP
address by using AutoIP.
o
AutoIP
: a protocol that automatically creates a link-local IP address based on the
EX2500A’s MAC address. If the IP address created is not available on a network, another
IP will be chosen randomly.