VOLCANO
VR Mini
VOLCANO
VR1
VOLCANO
VR2
VOLCANO
VR3
VOLCANO
VR-D Mini
VOLCANO
VR-D
10
VOLCANO
VR Mini
VOLCANO
VR1
VOLCANO
VR2
VOLCANO
VR3
VOLCANO
VR-D
4. ASSEMBLY
NOTE
Installation location should be suitably selected with special consideration of potential loads and vibrations.
Prior to any installation or maintenance works, disconnect the device from the power supply and secure it against accidental power-up.
Use filters in the hydraulic system. Before you connect the hydraulic lines (especially supply lines) to the device, you should clean/rinse the installation by draining two litres out of it.
NOTE
It is necessary to maintain a minimum distance of 0.4m from the wall or the ceiling; otherwise the device can malfunction, the fan can be damaged or its operating noise can increase.
If the device will be installed on a wall or under a ceiling, observe the following factors:
mounting height
OPT
. 2-5m (V
olcano V mini)
OPT
. 2,5-8m (V
olcano VR1, VR2, VR3)
OPT
. 3-8m (V
olcano V mini)
OPT
. 3-1
1m (V
olcano VR1, VR2)
OPT
. 3-12m (V
olcano VR3)
OPT
. 6-15m (V
olcano VR-D)
* for vertical air guides adjustment
distance between units – recommended distance 6-12m (Volcano VR1, VR2, VR3), 3-7m (Volcano VR Mini), in order to ensure even hot air diffusion
range of air stream
Max. 14m* (Volcano V mini)
Max. 22m* (Volcano VR1, VR2)
Max. 25m* (Volcano VR3)
Max. 28m* (Volcano VR-D)
Max. 2m** (Volcano V mini)
Max. 13m* (Volcano VR1, VR2)
Max. 15m* (Volcano VR3, VR-D)
* for horizontal air guide adjustment
** for symmetric air guide adjustment at an angle of 45°
device noise level (depending on acoustic characteristics of a room)
operation mode of the heating device, e.g. it can also operate as an air mixing device preventing air stratification
direction of air distribution should be controlled in a way that prevents draughts. Air stream must not be directed at walls, brackets, girders, cranes, shelves, machines, etc.
OPT. 3-7m
(Volcano VR Mini)
OPT. 6-12m
(Volcano VR1, VR2, VR3)
OPT
. 2-5m (V
olcano VR Mini)
OPT
. 2,5-8m (V
olcano VR1, VR2, VR3)
Volcano VR Mini
fan speed
III
II
I
air flow
m³/h
2100
1650
1100
noise level for Volcano AC*
dB(A)
52
42
29
noise level for Volcano EC*
dB(A)
50
40
27
AC motor electric power**
W
115
68
48
EC motor electric power**
W
95
56
39
electricity consumption**
W
91
32
5
horizontal air stream range
m
14
8
5
vertical air stream range
m
8
5
3
Volcano VR1
fan speed
III
II
I
air flow
m³/h
5300
3900
2800
noise level for Volcano AC*
dB(A)
56
51
40
noise level for Volcano EC*
dB(A)
54
49
38
AC motor electric power**
W
280
220
190
EC motor electric power**
W
250
190
162
electricity consumption**
W
202
75
41
horizontal air stream range
m
23
20
15
vertical air stream range
m
12
9
7
Volcano VR2
fan speed
III
II
I
air flow
m³/h
4850
3600
2400
noise level for Volcano AC*
dB(A)
56
51
40
noise level for Volcano EC*
dB(A)
54
49
38
AC motor electric power**
W
280
220
190
EC motor electric power**
W
250
190
162
electricity consumption**
W
226
89
45
horizontal air stream range
m
22
19
14
vertical air stream range
m
11
8
6
Volcano VR3
fan speed
III
II
I
air flow
m³/h
5700
4100
3000
noise level for Volcano AC*
dB(A)
57
51
45
noise level for Volcano EC*
dB(A)
55
49
43
AC motor electric power**
W
410
320
245
EC motor electric power**
W
370
285
218
electricity consumption**
W
355
123
55
horizontal air stream range
m
25
22
17
vertical air stream range
m
12
9
7
Volcano VR-D
fan speed
III
II
I
air flow
m³/h
6500
4600
3400
noise level for Volcano AC*
dB(A)
58
52
45
noise level for Volcano EC*
dB(A)
56
50
43
AC motor electric power**
W
410
320
245
EC motor electric power**
W
370
285
218
horizontal air stream range
m
28
24
19
vertical air stream range
m
15
11
9
Volcano VR-D Mini
fan speed
III
II
I
air flow
m³/h
2330
1830
1220
noise level for Volcano EC*
dB(A)
50
40
27
EC motor electric power**
W
95
56
39
horizontal air stream range
m
16
10
7
vertical air stream range
m
10
7
5
* reference conditions: room volume 1500m³,
measurement taken at a distance of 5m.
** EC motor electric power for the air flow mentioned in the table
*** Standard laboratory conditions
* reference conditions: room volume 1500m³,
measurement taken at a distance of 5m.
** EC motor electric power for the air flow mentioned in the table
*** Standard laboratory conditions
* reference conditions: room volume 1500m³,
measurement taken at a distance of 5m.
** EC motor electric power for the air flow mentioned in the table
*** Standard laboratory conditions
* reference conditions: room volume 1500m³,
measurement taken at a distance of 5m.
** EC motor electric power for the air flow mentioned in the table
*** Standard laboratory conditions
* reference conditions: room volume 1500m³,
measurement taken at a distance of 5m.
** EC motor electric power for the air flow mentioned in the table
*** Standard laboratory conditions
* reference conditions: room volume 1500m³,
measurement taken at a distance of 5m.
** EC motor electric power for the air flow mentioned in the table
*** Standard laboratory conditions
28