VOLCANO
VR Mini
VOLCANO
VR1
VOLCANO
VR2
VOLCANO
VR3
VOLCANO
VR-D Mini
VOLCANO
VR-D
11
Examples of arrangement of air heating units mounted on a wall
Top view
4.1 INSTALLATION WITH A BRACKET
The bracket is optional. In order to attach a bracket to the device, use crown drill bits to drill holes in the top and bottom panels of the heating unit (in places marked by
6
), and insert sleeves
into the holes. Slide holder arms onto the sleeves. Insert M10 screws into the top and bottom sleeves, and fix the bracket position in relation to the heater while tightening the screws. When you
adjust the device in the right position, fit plugs onto the bracket.
1
2
3
6
4
5
The bracket unit consists of:
1.
ARM (1 piece);
2.
HOLDER;
3.
M10 SCREW WITH A WASHER AND NUT FASTENING THE CLAMP (2 sets);
4.
M10 SCREW FASTENING THE HOLDER TO THE UNIT HEATER (2
pieces);
5.
PLUG (2 pieces);
6.
MOUNTING SLEEVE (2 pieces)
rotation of the device when mounted on a console
120
°
12
VOLCANO
VR Mini
VOLCANO
VR1
VOLCANO
VR2
VOLCANO
VR3
VOLCANO
VR-D
EXAMPLE OF A HYDRAULIC SYSTEM:
1.
UNIT HEATER;
2.
POWER-OPERATED VALVE;
3.
VENT VALVE;
4.
CUT-OFF VALVE;
5.
FILTER;
6.
CIRCULATION PUMP;
7.
BOILER
4.2 INSTALLATION INSTRUCTIONS AND MOUNTING DISTANCES
Installation of the heating medium supply system
While installing the piping for the heating medium, secure the exchanger connection against twisting
1
. The piping should not overload the
heater connections.
It is possible to connect the piping with flexible connections (adjustable angle of the airflow).
6
5
4
3
1
2
7
SUPPL
Y
RETURN
supply
supply
return
return
Volcano V mini
Volcano VR1, VR2, VR3
VOLCANO VR Mini, VR1, VR2, VR3
VOLCANO VR Mini
VOLCANO VR1, VR2, VR3, VR-D
12
EXAMPLE OF A HYDRAULIC SYSTEM:
1.
UNIT HEATER;
2.
POWER-OPERATED VALVE;
3.
VENT VALVE;
4.
CUT-OFF VALVE;
5.
FILTER;
6.
CIRCULATION PUMP;
7.
BOILER
4.2 INSTALLATION INSTRUCTIONS AND MOUNTING DISTANCES
Installation of the heating medium supply system
While installing the piping for the heating medium, secure the exchanger connection against twisting
1
. The piping should not overload the
heater connections.
It is possible to connect the piping with flexible connections (adjustable angle of the airflow).
6
5
4
3
1
2
7
SUPPL
Y
RETURN
supply
supply
return
return
Volcano V mini
Volcano VR1, VR2, VR3
VOLCANO VR Mini, VR1, VR2, VR3
VOLCANO VR Mini
VOLCANO VR1, VR2, VR3, VR-D
Note!
Maximum operating pressure of the medium for water coils is 16 bar, tested pressure: 21 bar
Requirements of the quality medium for the water coils:
Parameter
Value
Oil and grease
< 1 mg/l
pH at 25
o
C
8 to 9
Residual water hardness
[Ca2+, Mg2+]/[HCO3-] > 0.5
Oxygen
< 0.1 mg/l (as low as possible)
31
EN