8.
Verify incoming gas supply line pressure is
7“ Water Column (natural gas) and 11” Water
Column (propane).
If inlet pressure is excessive, contact the local gas
supply company to adjust incoming line pressure.
Fig. 43
9.
Verify combustion blower motor speed, control
board settings.
NOTE:
The head of the arrow cut out in the center will
designate the rotary switch setting. "F" and "8" are
designations on the potentiometer.
•
High Fire = F (1, Fig. 44)
•
Low Fire = 8 (2, Fig. 44)
Fig. 44
10. Turn fine adjustment screw on gas valve
clockwise all the way in. (Fig. 45)
11. Adjust gas valve fine adjustment screw for type
of gas. (Fig. 45)
A.
If unable to achieve correct pressure, then
replace GAS VALVE. Preset S2 - gas
pressure fine adjustment screw on the
replacement valve. Turn screw fully
clockwise until it stops.
•
Propane:
Turn fine adjustment screw on
gas valve counterclockwise 9 turns.
•
Natural Gas:
Turn fine adjustment screw on
gas valve counterclockwise 15 turns.
Fig. 45
12. Turn temperature control to
“BOIL”
and turn on
power switch to initiate ignition series.
13. After a warmup of 10 minutes begin sampling flue
gas with a calibrated analyzer.
Flue gasses must be checked with a combustion
analyzer. Combustion limits are listed below. If the
burner system fails to meet these requirements,
please call Steam Technical Support immediately.
Insert sampling probe into flue discharge, located
towards the rear of kettle. Ensure the probe is inserted
in such a way that the sample gas is not diluted. Place
the probe 1-2 inches below the discharge.
14. Make further adjustments to fine adjustment
screw if needed to obtain CO2 reading of 10.5%
to 12.0% (Natural Gas) or 12.0% to 13.5%
(propane).
15. Verify combustion analyzer reports CO air free of
less than 400ppm (.04%). If not, turn fine
adjustment screw CW to lower CO.
SPARK IGNITION TEST
If the ignition control module is not generating a spark
or the spark is not sufficient to light kettle burner,
perform the following test.
K Series Gas Kettles 2/3 Jacketed Stationary and Tilting - SERVICE PROCEDURES AND ADJUSTMENTS
F45461 Rev. B (1117)
Page 26 of 48